Plan Review Notes
Plan Review Notes For Permit 15080004
Permit Number 15080004
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-05 18:22:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 / 2008 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ELECTRICAL PLANS THAT ARE DRAWN
 TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER OR
 OTHER ACCEPTABLE MEDIUM WITH CONTRAST, CLARITY AND
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. FBC 107.1 &
 107.2.1.4
  
 2) SPECIFY THE LOCATION OF THE ELECTRIC METER AND
 SERVICE EQUIPMENT DISCONNECT. FBC 107.2.1 & NEC 230.70
  
 3) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH WALL COUNTERTOP SPACE 12 INCHES OR
 WIDER SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN
 2 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE.
  
 4) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS.
  
 5) A SEPARATE PERMIT IS REQUIRED FOR THE TEMPORARY
 ELECTRIC SERVICE. REMOVE THE TEMPORARY SERVICE DRAWING
 FROM THE PLANS. FBC 107.2.1
  
 6) NEC 220.40 - PROVIDE ACCURATE ELECTRICAL LOAD
 CALCULATIONS.
  
 7) NEC 406.8 - OUTDOOR RECEPTACLES ARE REQUIRED TO BE
 WEATHER PROOF.
  
 8) FBC 107.2.1 - SPECIFY THE LOCATIONS OF THE TWO AIR
 HANDLER UNITS ON THE PLANS AND SHOW COMPLIANCE WITH NEC
 110.32(B) FOR REQUIRED PERMANENT LADDERS TO PROVIDE
 SAFE ACCESS TO EQUIPMENT INSTALLED IN ATTICS.
  
 9) FBC 107.2.1 - SPECIFY THE LOCATION OF THE WATER
 HEATER ON THE PLANS AND THE DISCONNECT REQUIRED BY NEC
 422.31.
  
 10) NEC 210.52(D) AT LEAST ONE GFCI PROTECTED
 RECEPTACLE OUTLET IS REQUIRED IN THE BATHROOM AT
 BEDROOM #1.
  
 11) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE
 PRESENT.
  
 12) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 13) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 14) A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR GAS. IF THE APPLIANCES ARE INTENDED TO BE
 GAS THEY SHOULD BE SPECIFIED ON THE PLANS AS SUCH. FBC
 107.2.1
  
  
  
  
  