Plan Review Notes
Plan Review Notes For Permit 15071238
Permit Number 15071238
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-01 10:46:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS REFER TO FBC 2010; GOVERNING CODE CHANGED TO
 FBC 5TH EDITION (2014) EFFECTIVE JUNE 31, 2015. REVISE
 AS APPLICABLE. THE CODE SECTION REFERENCED ON THE PLAN
 (FBC 1029.4.1) IS FROM THE BUILDING CODE; IS THIS MULTI
 FAMILY AND GOVERENED BY THE FLORIDA BUILDING CODE,
 BUILDING RATHER THAN THE FLORIDA BUILDING CODE,
 RESIDENTIAL? CLARIFY.
  
 2. FBC 107, PROVIDE MORE INFORMATION REGARDING THE
 EXISTING EGRESS OPENINGS. PLEASE EXPLAIN HOW A 50" HIGH
 SINGLE HUNG WINDOW CAN HAVE A CLEAR OPENING OF 24".
  
 50" HIGH WINDOW / 2 (TOP PANE, BOTTOM PANE) = 25". 25"
 - 24" (ARCHITECT STATES THIS IS THE CLEAR OPENING) =
 1". PROVIDE A DETAIL OF THE EXISTING WINDOW TO SHOW HOW
 THE FRAME (TOP, BOTTOM) AND MEETING RAIL CAN EQUAL ONE
 INCH. FBC 5TH EDITION EXISTING BUILDING CODE 704.1
 ALLOWS A 5% REDUCTION IN CLEAR OPENING OF THE
 REPLACEMENT WINDOW. AS THE PLAN PROPOSES TO ELIMINATE A
 DOOR IN THIS BEDROOM, THEY CURRENTLY HAVE A COMPLIANT
 EMERGENCY MEANS OF ESCAPE AND RESCUE. THEREFORE THE NEW
 OPENING IS TO COMPLY WITH CURRENT CODE REQUIREMENTS.
 EXISTING WINDOWS DO NOT APPEAR TO COMPLY ALTHOUGH
 ARCHITECT HAS SIGNED AND SEALED A PLAN STATING THAT A
 50" WINDOW COMPLIES. COMPLIANCE FOR THIS LIFE SAFETY
 ITEM IS NOT CLEAR.
  
 WHEN RESUBMITTING, PLEASE HAVE ARCHITECT ADDRESS THIS
 COMMENT IN WRITING WITH AN EXPLANATION, OR HAVE
 ARCHITECT (NOT DRAFT PERSON) CALL ME. A SET HAS BEEN
 RETAINED.
  
 3. SEE FS481 AND FAC61G1. TITLE BLOCK TO INCLUDE
 PRINTED NAME AND LICENSE NUMBER, ARCHITECT BUSINESS
 NUMBER.
  
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/PRO/ARCH/STATUTES.
 HTML
  
 4. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH
 EDITION RESIDENTIAL 301.2.1.
  
 5. REVISE PLAN TO INCLUDE METHOD OF COMPLIANCE
 SELECTED, FBC 5TH EDITION EXISTING BUILDING CODE 301.1.
  
 6. STRUCTURAL DETAIL C A02 IS INSUFFICIENT. "REATTACH
 TRANSOM W/TAP CONS OR EQUIVALENT" - WHAT SIZE?
 FASTENING PATTERN?