Plan Review Notes For Permit 15071223 |
Permit Number |
15071223 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-05 10:32:58 | 114 SOUTH OLIVE AVENUE | | PERMIT #15071223 | | REVOKED PERMIT #14040237 | | MASTER #13060638 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISION***** | | | | THE BACKFLOW PREVENTER (INDICATING CONTROL VALVES) | | SHALL BE LOCATED IN A FIRE RATED ENCLOSURE ACCESSIBLE | | FROM THE EXTERIOR OR IN ACCORDANCE WITH NFPA 24 SECTION | | 6.2.1. | | | | PROVIDE FIRE DEPARTMENT CONNECTION ALONG OLIVE AVENUE. | | THE CURRENT ALLEY PLACEMENT IS NOT DESIRABLE AND IS TOO | | GREAT A DISTANCE FROM THE NEAREST FIRE HYDRANT. PER | | NFPA 14 SECTION 6.4.5.1 FIRE DEPARTMENT CONNECTIONS | | SHALL BE VISIBLE AND RECOGNIZABLE FROM THE STREET OR | | NEAREST POINT OF FIRE DEPARTMENT APPARATUS | | ACCESSIBILITY OR ON THE STREET SIDE OF BUILDINGS. | | CONNECTIONS SHALL BE LOCATED NOT MORE THAN 100 FEET | | FROM THE NEAREST FIRE HYDRANT CONNECTED TO AN APPROVED | | WATER SUPPLY. | | | | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | CONNECTION. | | | | CONFIRM THE RESTROOM STALL PARTITIONS ARE NOT SPRINKLER | | SPRAY OBSTRUCTIONS PER NFPA 13. ADDITIONAL SPRINKLERS | | MAY BE REQUIRED. | | | | ***NOTE: A SEPARATE PERMIT IS NEEDED FOR THE | | UNDERGROUND FIRE LINE (THIS MAIN IS NOT EXISTING)*** | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|