Plan Review Notes
Plan Review Notes For Permit 15071223
Permit Number 15071223
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-08-05 10:32:58114 SOUTH OLIVE AVENUE
 PERMIT #15071223
 REVOKED PERMIT #14040237
 MASTER #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE BACKFLOW PREVENTER (INDICATING CONTROL VALVES)
 SHALL BE LOCATED IN A FIRE RATED ENCLOSURE ACCESSIBLE
 FROM THE EXTERIOR OR IN ACCORDANCE WITH NFPA 24 SECTION
 6.2.1.
  
 PROVIDE FIRE DEPARTMENT CONNECTION ALONG OLIVE AVENUE.
 THE CURRENT ALLEY PLACEMENT IS NOT DESIRABLE AND IS TOO
 GREAT A DISTANCE FROM THE NEAREST FIRE HYDRANT. PER
 NFPA 14 SECTION 6.4.5.1 FIRE DEPARTMENT CONNECTIONS
 SHALL BE VISIBLE AND RECOGNIZABLE FROM THE STREET OR
 NEAREST POINT OF FIRE DEPARTMENT APPARATUS
 ACCESSIBILITY OR ON THE STREET SIDE OF BUILDINGS.
 CONNECTIONS SHALL BE LOCATED NOT MORE THAN 100 FEET
 FROM THE NEAREST FIRE HYDRANT CONNECTED TO AN APPROVED
 WATER SUPPLY.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 CONFIRM THE RESTROOM STALL PARTITIONS ARE NOT SPRINKLER
 SPRAY OBSTRUCTIONS PER NFPA 13. ADDITIONAL SPRINKLERS
 MAY BE REQUIRED.
  
 ***NOTE: A SEPARATE PERMIT IS NEEDED FOR THE
 UNDERGROUND FIRE LINE (THIS MAIN IS NOT EXISTING)***
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730