2015-08-08 18:42:12#1 EXIST DCDA MUST BE APPROVED FOR LOCATION FROM CITY
 OF WPB UTILITIES CUSTOMER SERVICE.
  
 #2 EXIST. BACFLOW MUST BE IN HORIZONTAL CONFIGURATION.
  
 #3 EXIST BACFLOW MUST BE ACCESSIBLE TO CITY OF WPB
 UTILITIES CUSTOMER SERVICE.
  
 #4 SUBMIT A SPECIFICATION SHEET FOR DCDA FOR APPROVAL
 TO [email protected] CC. [email protected]
 REFERENCE YOUR PERMIT #. ALTHOUGH I UNDERSTAND THIS IS
 THE OLD LOCATION OF THE DCDA
 PLEASE CONTACT STEPHEN HUNTER (561) 644-7329 CITY OF
 WPB UTILITIES CUSTOMER SERVICE
 TO MAKE A SITE VISIT AND MAKE SURE ALL THE COMMENTS ARE
 ADDRESSED,
  