Plan Review Notes For Permit 15071187 |
Permit Number |
15071187 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-08-05 09:16:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SUBSTRATE FOR HORIZONTAL INSTALLATIONS HAVE BEEN | | CHANGED TO CONCRETE BLOCK SUBSTRATE. THE ANCHOR WAS | | "PANELMATE" ON FIRST SUBMITTAL, BUT HAS BEEN CHANGED TO | | "ANCHOR & SCREW." PROPOSED ANCHOR SPACING REMAINED THE | | SAME. | | | | A. PLEASE REVISE ANCHOR TO BE CONSISTENT WITH THE | | PRODUCT APPROVAL. FOR INSTANCE, PAGE 5, SPACING FOR | | "ALL POINTS SOLID-SET" WAS CIRCLED. IF THIS IS THE | | ANCHOR PROPOSED, "1/4" SOLID SET" WOULD BE THE ANCHOR. | | "ANCHOR & SCREW" IS NOT LISTED AS ONE OF THE OPTIONS | | WITHIN THE PRODUCT APPROVAL. | | | | B. SUBSTRATE WAS CHANGED, AND ANCHOR SPACING FOR | | CONCRETE BLOCK, SPAN < 6 FT WAS CIRCLED. SEE ALL | | OPENINGS WITH A SPAN GREATER THAN 6' (EXAMPLE 1, 2, 3, | | ETC); THESE OPENINGS EXCEED 6' SO THE COLUMN FOR SPAN < | | 8.67 FT SHOULD BE USED. ANCHOR SPACING PROPOSED DOES | | NOT COMPLY WITH THE REQUIREMENTS OF THE PRODUCT | | APPROVAL. | | | | FBC 5TH EDITION RESIDENTIAL 301.1, WIND LOADS | | |
|