Plan Review Notes
Plan Review Notes For Permit 15071167
Permit Number 15071167
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-30 11:09:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A DIAGRAM THAT SHOWS THE
 DIMENSIONS OF THE SLOPED AND FLAT ROOF AREAS THAT ARE
 TO BE RE-ROOFED. FBC 107.2.1
  
 2) SPECIFY THE ROOF SLOPE AND THE MEAN ROOF HEIGHT. FBC
 107.2.1
  
 3) THE ROOF SYSTEM THAT WAS SELECTED FOR THE FLAT ROOF
 ON PAGE 8 OF NOA NO. 12-0703.06 HAS A MAXIMUM DESIGN
 PRESSURE OF -60 PSF. THIS IS NOT ADEQUATE FOR ALL OF
 THE ROOF ZONES AND REQUIRES ENHANCED FASTENING AS
 ALLOWED BY LIMITATION #7 ON PAGE 10 OF THE NOA. SUBMIT
 TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING IN ACCORDANCE WITH LIMITATION #7.
 FBC 107.2.1.3