Plan Review Notes For Permit 15071145
Permit Number 15071145
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-20 09:35:13ON SKENNEDY'S DESK
2015-08-07 08:12:48BUILDING PLAN REVIEW
 W. P. B. REVISION: 15071145
 W. P. B. PERMIT: 15010404
 ADD: 255 EVERNIA ST. UNIT MU3/1003
 CONT: BLUEWATER BUILDERS
 TEL: (561)373-2053
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 07/2015
 ACTION: DENIED
  
 1) PLEASE SEE SHEET M5.1 DETAIL # 1 SIDE WALL MOUNT A/C
 CONDENSER MOUNT AND BRAKET. THE PLANS INDICATE TO REFER
 TO MIAMI TECH ENGINEERING SHEET TO BE SEALED BY A
 REGISTERED FLORIDA P. E. THE MIAMI TECH ENGINEERING WAS
 NOT SUBMITTED. MAY REQUIRE PRODUCT APPROVAL IF THIS
 UNIT IS NOT A CUSTOM DESIGN AND WOULD NEED TO COMPLY
 WITH:
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS
  
 2) WITH NOT HAVING THE MIAMI TECH ENGINEERED SHEETS IT
 IS UNKNOWN IF THEY INCLUDE THE ATTACHMENT ANCHORS FOR
 THE STAND TO THE WALL. 2010 FBC- ADMINISTRATION.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. 2010
 FBC-B 1609.6.4. 4.1. COMPONENTS & CLADDING .
  
 3) THE PLANS ALSO FAIL TO SHOW THE CONNECTION FROM THE
 COMPRESSOR STAND TO THE COMPRESSOR. 2010 FBC-
 ADMINISTRATION. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. 2010 FBC-B 1609.6.4. 4.1. COMPONENTS &
 CLADDING .
  
 4) PLEASE PROVIDE THE WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676