Plan Review Notes
Plan Review Notes For Permit 15071116
Permit Number 15071116
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-30 16:24:101ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071116
 7/30/15
  
 1) SHEET M.2: REVISE THE O/A CALCULATIONS IN ACCORDANCE
 WITH SECTION 809.2 ALTERED SYSTEMS FBC-14 EXISTING
 BUILDING:
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 A) PLEASE NOTE THE CALCULATION TABLE ON THE PLAN IS
 REFERENCING THE OUTDATED 2010 FLORIDA MECHANICAL CODE.
 THE 2014 FLORIDA BUILDING CODES 5TH EDITION WENT INTO
 EFFECT 6/30/15
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  