Plan Review Notes For Permit 15071116 |
Permit Number |
15071116 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-30 16:24:10 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15071116 | | 7/30/15 | | | | 1) SHEET M.2: REVISE THE O/A CALCULATIONS IN ACCORDANCE | | WITH SECTION 809.2 ALTERED SYSTEMS FBC-14 EXISTING | | BUILDING: | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | PROCEDURE OF ASHRAE 62. | | A) PLEASE NOTE THE CALCULATION TABLE ON THE PLAN IS | | REFERENCING THE OUTDATED 2010 FLORIDA MECHANICAL CODE. | | THE 2014 FLORIDA BUILDING CODES 5TH EDITION WENT INTO | | EFFECT 6/30/15 | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|