Plan Review Notes For Permit 15071104 |
Permit Number |
15071104 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-20 09:37:35 | ON SKENNEDY'S DESK | 2015-08-18 09:34:01 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15071104 | | | | 1) SHEET M-1: THE OUTSIDE AIR CALCULATION INDICATES AHU | | 1-4, HOWEVER THE PLANS AND EQUIPMENT SCHEDULE INDICATE | | WCHP'S 1-5: PLEASE CLARIFY AND UPDATE THE ASHRAE 62.1 | | REFERENCE TO THE CURRENT 2010 STANDARD IN EFFECT. | | 2) REFER TO SECTION 809. FBC-14 EXISTING BUILDING CODE: | | ALTERED EXISTING SYSTEMS. | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | PROCEDURE OF ASHRAE 62.1. PLEASE REVISE THE PLANS TRO | | SHOW COMPLIANCE. | | 3) SUBMIT PRODUCT CUT SHEETS FOR THE STAINLESS STEEL | | HEAT PUMP WATER HOSES. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|