2015-08-20 09:37:35ON SKENNEDY'S DESK
2015-08-18 09:34:011ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071104
  
 1) SHEET M-1: THE OUTSIDE AIR CALCULATION INDICATES AHU
 1-4, HOWEVER THE PLANS AND EQUIPMENT SCHEDULE INDICATE
 WCHP'S 1-5: PLEASE CLARIFY AND UPDATE THE ASHRAE 62.1
 REFERENCE TO THE CURRENT 2010 STANDARD IN EFFECT.
 2) REFER TO SECTION 809. FBC-14 EXISTING BUILDING CODE:
 ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.1. PLEASE REVISE THE PLANS TRO
 SHOW COMPLIANCE.
 3) SUBMIT PRODUCT CUT SHEETS FOR THE STAINLESS STEEL
 HEAT PUMP WATER HOSES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719