Plan Review Notes For Permit 15071100 |
Permit Number |
15071100 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-30 16:31:02 | ELECTRICAL PROVISO TO PERMIT 15071100 | | 1. ALL REPLACEMENT RECEPTACLES SHALL COMPLY W/2011 NEC | | 406.4(D)(1) THROUGH 406.4(D)(6). | | 2. ALL CEILING LUMINAIRE OUTLETS SHALL BE LISTED TO | | SUPPORT 50# AS PER NEC 314.27 | | 3. YOU SHALL COMPLY WITH SMOKE & CARBON MONOXIDE | | DETECTOR REQUIREMENTS AS INDICATED IN FBC-R 314.3.1 | | |
|