Review Stop E
Sequence Number 3
Notes
Date Text
2015-08-24 19:18:30IT APPEARS THAT THE EC DID NOT UNDERSTAND WHAT WAS
 REQUIRED OF HIM FOR A PROPER SUBMITTAL. I CALLED HIM
 AND EXPLAINED IN SPANISH WHAT WAS REQUIRED. I TOLD HIM
 THAT THE NEMA 14-50 RECEPTACLE REQUIRES A GROUNDED
 CONDUCTOR (NEUTRAL). HE ARGUED THAT THE EQUIPMENT DID
 NOT REQUIRE A NEUTRAL. REGARDLESS THE PROPOSED DEVICE
 REQUIRES A NEUTRAL THEN IF NO NEUTRAL IS REQUIRED
 CHANGE THE RECEPTACLE TYPE. I ALSO TOLD HIM IN SPANISH
 THAT I WAS ASKING FOR SPECS ON THE DEVICE BEING
 INSTALLED.