Plan Review Notes For Permit 15071078 |
Permit Number |
15071078 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-08-24 19:18:30 | IT APPEARS THAT THE EC DID NOT UNDERSTAND WHAT WAS | | REQUIRED OF HIM FOR A PROPER SUBMITTAL. I CALLED HIM | | AND EXPLAINED IN SPANISH WHAT WAS REQUIRED. I TOLD HIM | | THAT THE NEMA 14-50 RECEPTACLE REQUIRES A GROUNDED | | CONDUCTOR (NEUTRAL). HE ARGUED THAT THE EQUIPMENT DID | | NOT REQUIRE A NEUTRAL. REGARDLESS THE PROPOSED DEVICE | | REQUIRES A NEUTRAL THEN IF NO NEUTRAL IS REQUIRED | | CHANGE THE RECEPTACLE TYPE. I ALSO TOLD HIM IN SPANISH | | THAT I WAS ASKING FOR SPECS ON THE DEVICE BEING | | INSTALLED. |
|