Plan Review Notes For Permit 15071043 |
Permit Number |
15071043 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-10-15 14:27:52 | MECHANICAL APPROVED WITH EXCEPTIONS. | | SUBMITTALS REQUIRED PRIOR TO 1ST INSPECTION: | | | | 1) ENERGY CALCULATIONS | | 2) EXTERIOR PIPE INSULATION AND UV PROTECTION. | | 3) WIND LOAD TIE DOWN ENGINEERING FOR THE ROOFTOP PIPE | | SUPPORT STANDS AND CURBS. | | 4) FIRE DAMPERS | | 5) FL. PRODUCT APPROVALS/MIAMI-DADE NOA'S FOR THE | | DRAINABLE O/A LOUVERS. | | | | PLEASE NOT ALL FUTURE MECHANICAL LAYOUT PLANS MUST | | CLEARLY SHOW THE LOCATIONS OF FIRE-RATED WALLS AND | | FIRE-RATED CEILING ASSEMBLIES. |
|