2015-10-07 15:11:391451 SOUTH OLIVE AVENUE
 PERMIT #15071043
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW: SHEET PE601 INDICATES, "CONTRACTOR SHALL
 SUBMIT SPRINKLER PLANS IN ACCORDANCE WITH 61G-15."
 HOWEVER, COMPLIANCE WITH FAC 61G15-32 IS THE
 RESPONSIBILITY OF THE ENGINEER OF RECORD. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE ITEMS
 SUCH AS THE POINT OF SERVICE FOR THE WATER SUPPLY, A
 LIST OF APPLICABLE NFPA STANDARDS APPLICABLE TO THE
 PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH
 ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 ORIGINAL COMMENT: ENGINEERED FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730