2015-10-14 14:48:50 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15071043 |
| ADD: 1451 S. OLIVE AVE. |
| CONT: GILBANE |
| TEL: (561)236-7052 / (954)444-8062 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W |
| * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| |
| |
| 1ST REVIEW |
| DATE: TUES. AUG. 11/2015 |
| ACTION: DENIED |
| |
| 1-12) COMPLIED. |
| |
| 13) NEW COMMENT, DEALS WITH THE MINIMUM ELEMENTS FOR |
| PLAN REVIEW:107.3.5.1.1. MINIMUM PLAN REVIEW CRITERIA |
| FOR BUILDINGSCOMMERCIAL BUILDINGS. |
| (5) 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| EARLY WARNING SMOKE EVACUATION SYSTEMS |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| PRE-ENGINEERED SYSTEMS |
| RISER DIAGRAM |
| |
| FLORIDA ADMINISTRATIVE CODE: FIRE SPRINKLERS |
| 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| SYSTEMS. |
| |
| (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| SOURCES. |
| |
| (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| APPLICABLE: (A-M). |
| |
| 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |