2015-08-12 15:32:19 | 1ST REVIEW 2014 FBC |
| |
| COMMENTS: |
| |
| 1.PLEASE INDICATE ON THE PLANS OCCUPANCY LOAD AND |
| CALC.. |
| PB AMENDMENTS TO FBC 2014 SEC. 107.2.1.3 |
| 2.PLEASE INDICATE ON THE PLANS OCCUPANCY CLASSIFICATION |
| THIS IS A MIXED OCCUPANCY BUILDING, INDICATE WHICH BATH |
| SERVES WHICH OCCUPANCY. |
| WPB AMENDMENTS TO FBC 2014 SEC.107.2.1.3 |
| 3.PLEASE SHOW DEMINTIONS FOR SHOWER SEAT SHALL COMPLY |
| WITH. |
| FBCA SEC. 610.3.2 |
| 4.SHOWER CONTROLS ARE SHOWN ON OPPOSITE WALL FROM SEAT |
| ELEVATION 1/A PG. AE 614 CONTROLS SHALL BE ON ADJACENT |
| WALL FROM SEAT.TO COMPLY N. |
| FBCA SEC. 608.5.2 |
| 5. SHOW DETAIL ON DEMINTIONS FOR GRAB BARS IN TOILET |
| ROOM . |
| SIDE WALL SHALL COMPLY WITH 604.5.1 |
| REAR WALL SHALL COMPLY WITH 604.5.2 |
| 6.SHOW DETAIL FOR KNEE AND TOE CLEARANCE ON BREAK ROOM |
| SINKS AND LAVATORY'S IN BATHROOMS SHALL COMPLY WITH. |
| FBCA SEC. 306.2 AND 306.3 |
| 7. SHOW CLEAR FLOOR SPACE FOR BREAK ROOM SINKS |
| ,LAVATORY'S, SHOWER AND TOILETS SHALL COMPLY WITH . |
| FBCA SEC. 305 |
| 8.SHOW RISER DIAGRAM FOR SANITARY IN BATHROOM C-158 TO |
| COMPLY WITH. |
| WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13] |
| 9. DOMESTIC WATER RISER NOT COMPLETE MISSING RM |
| C-158,4IN. CW MAIN AND P-11.MUST SHAOW ALL WATER LINE |
| IN THIS PHASE. |
| WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13] |
| 10COPE OF WORK ON THIS PROJECT IS UNCLEAR .IS PLUMBING |
| ON THIRD FLOOR CHANGING , |
| WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13 |
| |
| |
| 11. PLEASE CLARIFY WHAT PHASE OF THIS PROJECT IS UNDER |
| THIS PERMIT AND WHAT PHASES WILL BE UNDER OTHER PERMIT |
| SOME SYSTEMS WILL OVERLAP AND I NEED ADDITIONAL |
| INFORMATION TO DO A THOROUGH REVIEW. |
| WPB AMENDMENTS TO FBC 2014 SEC.107.3.5.1.3[13 |
| |
| |