2015-08-10 15:03:131ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071043
  
 1) DESIGN CRITERIA: PROVIDE ON THE PLAN A LIST OF
 CURRENT CODES AND STANDARDS USED FOR DESIGN AND
 INSTALLATION OF THE PROPOSED HVAC SYSTEM(S)
 ALTERATIONS.
 2) PROVIDE A NARRATIVE TO CLARIFY THE SCOPE AND EXTENT
 OF THE PROJECT PROJECT TO BE COVERED UNDER THIS PERMIT
 APPLICATION. BASED ON THE THE PHASING DIAGRAMS ON SHEET
 AE002 IT APPEARS THAT THE SUBMITTED PLANS WILL LIMIT
 THE PROJECT TO THE NORTH SIDE ALTERATIONS CULMINATING
 AT STAGE 2, AND WILL NOT INCLUDE THE EXPANSION ON THE
 WEST AND SOUTH SIDES.
 3) REFERENCE THE FBC-14 EXISTING BUILDING CODE, SECTION
 809.2 ALTERED EXISTING SYSTEMS: IN MECHANICALLY
 VENTILATED SPACES, EXISTING MECHANICAL VENTILATION
 SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR EXTENDED
 SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER MINUTE
 (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR AND NOT
 LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION AIR PER
 PERSON; OR NOT LESS THAN THE AMOUNT OF VENTILATION AIR
 DETERMINED BY THE INDOOR AIR QUALITY PROCEDURE OF
 ASHRAE 62. PLEASE PROVIDE A VENTILATION SCHEDULE ON THE
 PLAN INDICATING THE REQUIRED CFM'S OF O/A PER THE
 REFERENCED SECTION, AND THE CFM'S OF O/A TO BE
 PROVIDED. SEE ALSO TABLE 403.3 FBC-14 MECHANICAL.
 4) SIZING CALCULATIONS ARE REQUIRED FOR AHU'S 25,
 26,27,28, & 29. REFERENCE THE FBC-14 ENERGY
 CONSERVATION CODE, SECTION C403.2.1 C403.2.1
 CALCULATION OF HEATING AND COOLING LOADS:
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 5) PROVIDE CHILLED AND HOT WATER PIPING AND VALVE
 SCHEDULES, AND INSTALLATION NOTES AND DETAILS.
 6) REFERENCE SECTION C403.4.5 FBC-14 ENERGY
 CONSERVATION AND SHOW COMPLIANCE- REQUIREMENTS FOR
 COMPLEX MECHANICAL SYSTEMS SERVING MULTIPLE ZONES:
 SECTIONS C403.4.5.1 THROUGH C403.4.5.4 SHALL APPLY TO
 COMPLEX MECHANICAL SYSTEMS SERVING MULTIPLE ZONES.
 SUPPLY AIR SYSTEMS SERVING MULTIPLE ZONES SHALL BE VAV
 SYSTEMS WHICH, DURING PERIODS OF OCCUPANCY, ARE
 DESIGNED AND CAPABLE OF BEING CONTROLLED TO REDUCE
 PRIMARY AIR SUPPLY TO EACH ZONE TO ONE OF THE FOLLOWING
 BEFORE REHEATING, RECOOLING OR MIXING TAKES PLACE:
 1. THIRTY PERCENT OF THE MAXIMUM SUPPLY AIR TO EACH
 ZONE.
 2. THREE HUNDRED CFM (142 L/S) OR LESS WHERE THE
 MAXIMUM FLOW RATE IS LESS THAN 10 PERCENT OF THE TOTAL
 FAN SYSTEM SUPPLY AIRFLOW RATE.
 3. THE MINIMUM VENTILATION REQUIREMENTS OF CHAPTER 4 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
  
 EXCEPTION: THE FOLLOWING DEFINE WHERE INDIVIDUAL ZONES
 OR WHERE ENTIRE AIR DISTRIBUTION SYSTEMS ARE EXEMPTED
 FROM THE REQUIREMENT FOR VAV CONTROL:
 1. ZONES WHERE SPECIAL PRESSURIZATION RELATIONSHIPS OR
 CROSS-CONTAMINATION REQUIREMENTS ARE SUCH THAT VAV
 SYSTEMS ARE IMPRACTICAL.
 2. ZONES OR SUPPLY AIR SYSTEMS WHERE AT LEAST 75
 PERCENT OF THE ENERGY FOR REHEATING OR FOR PROVIDING
 WARM AIR IN MIXING SYSTEMS IS PROVIDED FROM A
 SITE-RECOVERED OR SITE-SOLAR ENERGY SOURCE.
 3. ZONES WHERE SPECIAL HUMIDITY LEVELS ARE REQUIRED TO
 SATISFY PROCESS NEEDS.
 4. ZONES WITH A PEAK SUPPLY AIR QUANTITY OF 300 CFM
 (142 L/S) OR LESS AND WHERE THE FLOW RATE IS LESS THAN
 10 PERCENT OF THE TOTAL FAN SYSTEM SUPPLY AIRFLOW RATE.
 5. ZONES WHERE THE VOLUME OF AIR TO BE REHEATED,
 RECOOLED OR MIXED IS NO GREATER THAN THE VOLUME OF
 OUTSIDE AIR REQUIRED TO MEET THE MINIMUM VENTILATION
 REQUIREMENTS OF CHAPTER 4 OF THE FLORIDA BUILDING CODE,
 MECHANICAL.
 6. ZONES OR SUPPLY AIR SYSTEMS WITH THERMOSTATIC AND
 HUMIDISTATIC CONTROLS CAPABLE OF OPERATING IN SEQUENCE
 THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONES
 AND WHICH ARE CAPABLE OF PREVENTING REHEATING,
 RECOOLING, MIXING OR SIMULTANEOUS SUPPLY OF AIR THAT
 HAS BEEN PREVIOUSLY COOLED, EITHER MECHANICALLY OR
 THROUGH THE USE OF ECONOMIZER SYSTEMS, AND AIR THAT HAS
 BEEN PREVIOUSLY MECHANICALLY HEATED.
  