2015-08-12 14:09:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15071043
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: (561)236-7052 / (954)444-8062
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
  
 1ST REVIEW
 DATE: TUES. AUG. 11/2015
 ACTION: DENIED
  
 1) THERE IS NO CODE ANALYSIS ON EITHER THE PHASING PLAN
 AE002 NOR ANY OF THE LIFE SAFETY PLANS LS 01, LS01M OR
 LS 03 PROVIDING HOW CODE COMPLIANCE IS TO BE ACHIEVED.
 THE MEETING HELD JUNE 09/2015 WENT INTO GREAT LENGTH
 ALLOWANCES AND OR EXCEPTIONS THE DESIGNER OF RECORD
 WOULD LIKE THE CITY TO CONSIDER, BUT THERE HAS BEEN NO
 FORMAL (WRITTEN) REQUEST TO THE BUILDING OFFICIAL UNDER
 THE 2014 FLORIDA BUILDING CODE, CHAPTER 1 (A) 104.11
 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT
 THE INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY
 DESIGN OR METHOD OF CONSTRUCTION NOT SPECIFICALLY
 PRESCRIBED BY THIS CODE, PROVIDED THAT ANY SUCH
 ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL BE APPROVED
 WHERE THE BUILDING OFFICIAL FINDS THAT THE PROPOSED
 DESIGN IS SATISFACTORY AND COMPLIES WITH THE INTENT OF
 THE PROVISIONS OF THIS CODE, AND THAT THE MATERIAL,
 METHOD OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY.
  
 [A] 104.11.1 RESEARCH REPORTS.
 SUPPORTING DATA, WHERE NECESSARY TO ASSIST IN THE
 APPROVAL OF MATERIALS OR ASSEMBLIES NOT SPECIFICALLY
 PROVIDED FOR IN THIS CODE, SHALL CONSIST OF VALID
 RESEARCH REPORTS FROM APPROVED SOURCES.
  
 [A] 104.11.2 TESTS.
 WHENEVER THERE IS INSUFFICIENT EVIDENCE OF COMPLIANCE
 WITH THE PROVISIONS OF THIS CODE, OR EVIDENCE THAT A
 MATERIAL OR METHOD DOES NOT CONFORM TO THE REQUIREMENTS
 OF THIS CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR
 ALTERNATIVE MATERIALS OR METHODS, THE BUILDING OFFICIAL
 SHALL HAVE THE AUTHORITY TO REQUIRE TESTS AS EVIDENCE
 OF COMPLIANCE TO BE MADE AT NO EXPENSE TO THE
 JURISDICTION. TEST METHODS SHALL BE AS SPECIFIED IN
 THIS CODE OR BY OTHER RECOGNIZED TEST STANDARDS. IN THE
 ABSENCE OF RECOGNIZED AND ACCEPTED TEST METHODS, THE
 BUILDING OFFICIAL SHALL APPROVE THE TESTING PROCEDURES.
 TESTS SHALL BE PERFORMED BY AN APPROVED AGENCY. REPORTS
 OF SUCH TESTS SHALL BE RETAINED BY THE BUILDING
 OFFICIAL FOR THE PERIOD REQUIRED FOR RETENTION OF
 PUBLIC RECORDS.
  
 2) THROUGHOUT THE PLANS ARCHITECTURAL AND STRUCTURAL
 PLANS THERE IS MENTION THAT THE PLANS HAVE BEEN
 DESIGNED TO THE 2012 IBC. PLEASE MAKE CORRECTION THAT
 ON JUNE 30, 2015 THE 5TH EDITION OF THE FLORIDA
 BUILDING CODE OR THE 2014 FBC WAS ADOPTED STATEWIDE.
 PLEASE MAKE CORRECTIONS. EXAMPLE UNDER THE 2014 FBC-B
 THERE IS NO SECTION 1704. RESERVED. SPECIAL
 INSPECTIONS.
  
 3) WITH THE STRUCTURAL RENOVATION AND ADDITION THIS
 BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 3G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4) THERE ARE SEVERAL REFERENCES TO THE 2012 IBC PLEASE
 BE AWARE THAT THE STATE OF FLORIDA IS UNDER THE 5TH
 EDITION OF THE FLORIDA BUILDING CODE, OR THE 2014 FBC.
 THE CURRENT EDITION OF THIS CODE WAS ADOPTED STATEWIDE
 JUNE 30/ 2015. PLEASE UPDATE CODE.
  
 5) THE SCOPE OF THIS PROJECT IS NOT CLEAR AS TO WHAT
 PHASES OF THE PROJECT IS REPRESENTED WITHIN THE PERMIT
 APPLICATION. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED TO BE ABLE TO DO A THOROUGH REVIEW.
  
 6) SHEET 043-SE-002 FOUNDATION INDICATES THERE WAS A
 SOILS INVESTIGATION COMPLETED, PLEASE SUBMIT THE REPORT
 COMPILED BY ARDAMAN & ASSOCIATED PHASE 1 EXPANSION.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS.
  
 7) SHEET 004-SE-003 STRUCTURAL OBSERVATION IS AGAIN
 REFERENCE THE 2012 IBC SECTION 1704. 2014 FBC-B
 RESERVED.
  
 8) SHEET 034-AE-801 THE DOOR SCHEDULE INDICATES NEW
 EXTERIOR DOORS AND SHEET 035-AE-811 INDICATES NEW
 STOREFRONT GLAZING SYSTEM. NOTE THE CONTRACTOR HAS NOT
 SUBMITTED ANY PRODUCT APPROVALS FOR THESE ITEMS. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS
  
 9) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 10) I COULD NOT FIND THE WIND DESIGN FOR THE NEW
 EXTERIOR WINDOW AND DOOR OPENINGS ON THE STRUCTURAL
 SHEETS. 2014 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 10.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 10.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 10.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 10.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT,
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 10.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2).
  
 11) SHEET 0013- AE121.4
  
 11A) PLANS INDICATE A WOOD SHOP ROOM C164 BUT THERE IS
 NO DOORS OR WALLS DEFINING THIS ROOM AND THE ART
 LANDING ROOM C163. PLEASE PROVIDE WHAT ACTIVITIES OCCUR
 IN THIS ROOM, IS THERE SAW DUST MADE, IF SO HOW MUCH
 DAILY? SEE COMBUSTIBLE DUST IN THE 2014 FBC-B TABLE
 415.10.1.1.1 QUANTITY LIMITS FOR HAZARDOUS MATERIALS IN
 A SINGLE FABRICATION AREA. LOOSE SEE FOOTNOTE B.
  
 11B) THE PLANS DO NOT SHOW WHAT WALLS ARE RATED,
 STAIRWELLS, PLEASE SHOW THE OCCUPANT LOADS FOR THE
 STAIR ENCLOSURE 1 & 2. PLEASE PROVIDE THE OCCUPANT LOAD
 FOR EACH FLOOR THE STAIRWELL OPENS ONTO AND THE AMOUNT
 OF OCCUPANTS EACH OF THE STAIRWELLS CAN HANDLE. 2014
 FBC-B 105.3.1 / 0.2 PER OCCUPANT SPRINKLERED BUILDINGS.
  
 11C) ROOM C170 MOTHERS ROOM IS UNDERNEATH STAIR 1A
 PLEASE SHOW COMPLIANCE WITH HOW THE STAIRWELL IS FIRE
 RATED AND THE AREA BENEATH THE STAIRWELL. FBC-B
 1009.3.1 (1) HOUR FIRE BARRIER.
  
 12) SHEET AE123.4 THIS PLAN SHOWS A NEW FLOOR OPENING
 BELOW AND WALL WITH NO DOOR OPENING INTO THE STAIRWELL.
 PLANS ARE NOT CLEAR AS TO THE INTENT. 107.2.1.4.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  