2015-10-15 09:36:162ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071040
 10/6/15
  
 1) THE ENERGY EFFICIENCY COMPLIANCE FORMS FOR THE TWO
 MODULAR OFFICES DO NOT SHOW ANY AC SYSTEM COMPLIANCE
 DATA- PLEASE REVISE THE FORMS.
 2) AS PREVIOUSLYY REQUESTED IN THE 1ST REVIEW, PROVIDE
 AC COOLING AND HEATING CALCULATIONS IN COMPLIANCE WITH
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER