2015-08-18 11:09:401ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071040
  
 1) REFER TO SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION- CALCULATION OF HEATING AND COOLING LOADS:
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 PLEASE SUBMIT UP TO DATE CALCULATIONS FOR NEW SYSTEM
 INSTALLATIONS, OR IF THE UNITS ARE EXISTING, SUBMIT
 COPIES OF THE ORIGINAL CALCULATIONS.
 2) REFER TO SECTION C101 AMD SUBMIT ENERGY CALCULATIONS
 FOR THE PROPOSED OFFICE TRAILER. PLEASE NOTE THAT
 COPIES OF THE ORIGINAL CALCULATIONS MAY BE SUBMITTED IF
 NO MODIFICATIONS TO THE MODULAR SINCE THAT TIME HAVE
 BEEN DONE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER