2015-09-11 10:27:12 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| PAGE EX-1 |
| 1. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE |
| ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN |
| FOR INSPECTION. UNDERGROUND SERVICE CONDUCTORS SHALL |
| COMPLY WITH NEC 300.5 |
| PAGE E-1 |
| 1. REDO YOUR MATH: 10917 X 6 = 65.5 KVA + 180 = 65.7 |
| KVA, 65.7 / 240 = .273 X 1000 = 273 AMP |
| 2. THIS DESCRIPTION OF THE PANEL DOES NOT MATCH THAT AS |
| MENTIONED BELOW. |
| 3. PER NEC 406.8: THIS DEVICE NOT ONLY REQUIRES AN |
| IN-USE TYPE COVER, BUT IT SHALL BE RATED/LISTED WEATHER |
| RESISTANT AS WELL. |
| 4. A 500 KCML CONDUCTOR IS NOT ACCEPTABLE TO BE |
| PROTECTED WITH A 400 AMP MCB. (380 AMP PER TABLE |
| 310.15) 2/250 KCML 510 AMP |
| 5. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE |
| ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN |
| FOR INSPECTION. UNDERGROUND SERVICE CONDUCTORS SHALL |
| COMPLY WITH NEC 300.5 |
| 6. THE TRAILERS AS AN ASSEMBLY ARE PERMITTED AND |
| INSPECTED BY OTHER, BUT THE SERVICE TO EACH IS PART OF |
| THE SCOPE OF THIS PERMIT, THEREFORE, SHOW ON THE RISER |
| THE FEEDERS TO EACH SUB-PANEL IN EACH TRAILER. |
| ACCORDING TO THE SITE-INSTALLED ITEMS LIST, THE MAIN |
| ELECTRICAL PANELS SHALL BE INSTALLED ON MULTI-UNIT |
| ASSEMBLIES. THERE APPEAR TO BE TWO (2) THREE UNIT |
| ASSEMBLIES BEING INSTALLED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU |
| |