2015-08-20 09:15:50BELOW IS A COPY OF THE PREVIOUS DENIAL COMMENTS. FROM
 THE LIST THE ONLY THING WHICH WAS DONE WAS TO LABEL THE
 VARIOUS ROOMS. YOU SHALL INDICATE WHAT IS NEW AND WHAT
 IS EXISTING.
 YOU SHALL ALSO INDICATE THE LOCATION OF THE SIX HI-HATS
 BEING INSTALLED, AND MAKE SURE THEY COMPLY WITH THE
 VARIOUS REQUIREMENTS OF THE NEC.
 THERE ARE SPECIFIC CODE REQUIREMENTS FOR REPLACEMENTS
 DEVICES EXPRESSED IN SECTION 406.4
 YOU SHALL PROVIDE A RISER DIAGRAM AND LOAD CALCS ALONG
 WITH A CIRCUIT DIRECTORY (PANEL SCHEDULE)
  
 IF YOU ARE HAVING TROUBLE WITH THIS, PLEASE DO NOT
 HESITATE TO CALL ME.
  
 (PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE VARIOUS ROOM WITHIN THIS DWELLING HAVE TO BE
 IDENTIFIED/LABELED.
 2.THE NEW HI-HAT HAVE TO COMPLY WITH NEC 410.110
 3. PROVIDE A RISER DIAGRAM INDICATING ALL NEW VS.
 EXISTING WORK.)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS
  
 THIS THIRD REVIEW STOP WAS CREATED BECAUSE I GOT LOCKED
 OUT O F THE PREVIOUS STOP.
  