2015-08-20 09:15:50 | BELOW IS A COPY OF THE PREVIOUS DENIAL COMMENTS. FROM |
| THE LIST THE ONLY THING WHICH WAS DONE WAS TO LABEL THE |
| VARIOUS ROOMS. YOU SHALL INDICATE WHAT IS NEW AND WHAT |
| IS EXISTING. |
| YOU SHALL ALSO INDICATE THE LOCATION OF THE SIX HI-HATS |
| BEING INSTALLED, AND MAKE SURE THEY COMPLY WITH THE |
| VARIOUS REQUIREMENTS OF THE NEC. |
| THERE ARE SPECIFIC CODE REQUIREMENTS FOR REPLACEMENTS |
| DEVICES EXPRESSED IN SECTION 406.4 |
| YOU SHALL PROVIDE A RISER DIAGRAM AND LOAD CALCS ALONG |
| WITH A CIRCUIT DIRECTORY (PANEL SCHEDULE) |
| |
| IF YOU ARE HAVING TROUBLE WITH THIS, PLEASE DO NOT |
| HESITATE TO CALL ME. |
| |
| (PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| 1. THE VARIOUS ROOM WITHIN THIS DWELLING HAVE TO BE |
| IDENTIFIED/LABELED. |
| 2.THE NEW HI-HAT HAVE TO COMPLY WITH NEC 410.110 |
| 3. PROVIDE A RISER DIAGRAM INDICATING ALL NEW VS. |
| EXISTING WORK.) |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS |
| |
| THIS THIRD REVIEW STOP WAS CREATED BECAUSE I GOT LOCKED |
| OUT O F THE PREVIOUS STOP. |
| |