2015-08-05 08:38:501ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071004
 8/5/15
  
 1) SHEET M-1: THE OUTSIDE AIR CALCULATION SCHEDULE IS
 REFERENCING THE OUTDATED ASHRAE 62.1- 2004. PLEASE
 REVIEW AND REVISE THE CALCULATIONS IN COMPLIANCE WITH
 SECTION 809.2 FBC-14 EXISTING BUILDING CODE: ALTERED
 EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 2) M-2: THE AIR DISTRIBUTION TAG PRINT AT THE DIFFUSERS
 IS TOO SMALL TO READ. PLEASE ENLARGE EITHER THE TAGS OR
 THE ENTIRE DRAWING TO EXPEDITE THE REVIEW- SECTION
 107.2.1 WPB AMENDEMENTS TO THE FBC-14 BUILDING CODE.
 3) M-2: LABEL (VAV 6-7) ON THE PLAN AS "NEW"
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER