2015-07-27 12:12:25 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | PER NFPA 101, CHAPTER 7 - 7.2.2.4.5.2 | | GUARDS SHALL NOT BE LESS THAN 42 IN. HIGH, EXCEPT AS | | PERMITTED BY ONE OF THE FOLLOWING: THE THREE EXCEPTION | | DO NOT APPLY TO THIS INSTALLATION. | | | | THE GUARDS SHALL NOT BE LESS THAN 42 IN. | | | | THE FIRE INSPECTOR SHALL CONFIMR THE HEIGHT ON FINAL | | FIRE INSPECTION. | | |
|