Plan Review Notes
Plan Review Notes For Permit 15070952
Permit Number 15070952
Review Stop B
Sequence Number 8
Notes
Date Text
2017-03-29 14:07:06RESIDENTIAL (R3) ALTERATION, 8TH BUILDING REVIEW
 CHECKLIST. (REAR BUILDING).
 CODE: FBC-5TH EDITION (2014).
  
 1- INFORMATION SUBMITTED IN THE DESIGN CRITERIA ON
 SHEETS A-1 AND A-2 IS NOT CLEAR. CLARIFY WHAT IS THE
 EXTERNAL = -0.9, INTERNAL - 0.2 AND NET UPLIFT
 COEFFICIENT=1.1 AND WHERE WERE IS THIS INFORMATION
 TAKEN FROM. ENGINEER OF RECORD TO PROVIDE CLARIFICATION
 IN WRITING. SEC. 107.2.1 AND 107.2.1.3 CITY AMENDMENTS.
 RESPONSE: RESPONSE LETTER STATES THAT "ALL REFERENCES
 WERE TAKEN FROM ASCE 7-10 AS FOLLOWS: EXTERNAL PRESSURE
 COEFFICIENT CHAPTER 30.2.4 TABLE 30.3.1. INTERNAL
 PRESSURE COEFFICIENT TAKEN FROM CH. 26.11.1. NET UPLIFT
 COEFFICIENT TAKEN FROM CH. 27". THIS PARTIAL DESIGN
 INFORMATION DOESN'T SEEM TO MAKE SENSE AND SEEMS TO BE
 INCORRECT.
  
 2- TWO STORY WALL SECTION ON SHEET A-2:
 A) REVISE ROOF SHEATHING FASTENING TYPE AND SPACING.
 SEE SEC. R803. 2.3.1 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED.
 REPEAT COMMENT. ENGINEER NOW SPECIFIED "8D CORREGATED
 NAILS 4" @ EDGE 9" ELSEWHERE". CLEARLY IDENTIFY WHAT'S
 A 8D CORREGATED NAIL. ALSO, TYPE OF NAIL AND SPACING
 LOOKS LESS STRONGER THAN THE MINIMUM REQUIRED BY SEC.
 R803.2.3.1. ENGINEER TO PROVIDE CALCULATIONS SHOWING
 THAT THE PROPOSED NAIL TYPE AND SPACING IS EQUAL OR
 BETTER THAN THE REQUIRED BY CODE.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 B) REVISE ROOF FRAMING FASTENERS. R301.1
 FBC-RESIDENTIAL.
 REPEAT COMMENT. FASTENERS SPECIFIED NOW DON'T MATCH
 FASTENERS SPECIFIED ON THE REVISED ROOF FRAMING PLAN.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 C) SPECIFY ROOF INSULATION. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. ENGINEER SPECIFIED R-30 ROOF
 INSULATION. CLEARLY SPECIFIED WHAT KIND OF INSULATION
 IS GOING TO BE INSTALLED. IF USING R-30 BATT
 INSULATION, THEN IT CAN NOT BE USED BECAUSE R-30 BATT
 INSULATION DOESN'T FIT ON 2 X 8 ROOF RAFTERS. THE
 THICKNESS OF R-30 BATT IS ABOUT 9-1/2". IN ADDITION IT
 DOESN'T ALLOW THE 1" SPACE BETWEEN INSULATION AND ROOF
 SHEATHING REQUIRED BY SEC. R806.3 FOR VENTILATION.
 REVISE AS REQUIRED.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 D) CLARIFY HOW THE SPECIFIED ROOF VENTILATION PROVIDE
 CROSS VENTILATION TO ENTIRE ROOF AS REQUIRED BY SEC.
 R806 FBC-RESIDENTIAL.
 REPEAT COMMENT. ENGINEER SPECIFIED 2" HOLE WITH SCREEN
 COVER FOR VENT EVERY OTHER RAFTER @ EA. END. THIS ONLY
 PROVIDES VENTILATION AT EVERY OTHER RAFTER. WHAT ABOUT
 CROSS VENTILATION FOR THE OTHER RAFTERS? .
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 E) A) WHAT'S IS THE "2 X 2 BELOW" SHOWN ON THE SECOND
 FLOOR BY THE ROOF AREA?. SEC. 107.2.1 CITY AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 F) ENGINEER SPECIFIED 2" HOLE WITH SCREEN COVER FOR
 VENT EVERY OTHER RAFTER @ EA. END. PROVIDE
 SPECIFICATIONS SHOWING HOW THE PROPOSED HOLES PROVIDE
 WATER RESISTANCE FROM THE WIND DRIVEN RAIN. SEC.
 R703.1.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 G) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE ROOF EAVE SHOWN N ON REVISED PLANS.
 SPECIFY ALL FRAMING MEMBERS AND FASTENERS. SEC. R301.1
 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 H) NEED TO SPECIFY ROOF GUTTERS AS REQUIRED BY SEC.
 R318.5 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE INSTALLATION OF ROOF GUTTERS.
 NOTE: COORDINATE WITH ITEM #3(G) ABOVE.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 I) SPECIFY ON PLANS THE ROOF SLOPE AS REQUIRED BY SEC.
 R905.11.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 3- ENERGY CALCULATIONS SUBMITTED;
 A) NEED TO PROVIDE THE NAME OF THE PERSON RESPONSIBLE
 FOR THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. NOT ADDRESSED AT ALL. NEED THE NAME OF
 THE PERSON WHO PREPARED THE ENERGY CALCULATIONS. ONLY A
 SIGNATURE WAS PROVIDED. SIGNATURE IS NOT A NAME. UNABLE
 TO IDENTIFY WHO PREPARED THEM.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME ENERGY
 CALCULATIONS WERE RE-SUBMITTED.
  
 B) CEILING INSULATION ITEM #10. NEW PLANS CALL FOR 2 X
 8 ROOF JOISTS. R30 BATT INSULATION DOESN'T FIT ON A 2 X
 8 SPACE. BATT INSULATION IS +/- 9-1/2" THICK. IN
 ADDITION L NEED AT LEAST 1" CLEAR SPACE FOR CROSS
 VENTILATION. REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. THIS NEEDS TO BE COORDINATED WITH THE
 ENGINEER OF RECORD. PLANS NEED TO BE REVISED. REVISE
 THE ENERGY CALCULATIONS ONCE THE PLANS ARE REVISED TO
 COMPLY WITH THE INSULATION AND VENTILATION
 REQUIREMENTS.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME ENERGY
 CALCULATIONS WERE RE-SUBMITTED.
  
 C) SIZE OF A/C UNIT SHOWN ON ITEM #12 SEEMS TO BE TOO
 SMALL FOR THE SIZE OF THE APARTMENT. THIS ITEM NEEDS TO
 BE COORDINATED WITH THE A/C EQUIPMENT SIZING
 CALCULATIONS. SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 REPEAT COMMENT. SIZE OF EQUIPMENT SPECIFIED ON PREVIOUS
 ENERGY CALCULATIONS WAS TOO BIG NOW SIZE SPECIFIED
 SEEMS TO BE TOO SMALL. THIS NEEDS TO BE COORDINATED
 BEFORE REVISING THE ENERGY CALCULATIONS.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME ENERGY
 CALCULATIONS WERE RE-SUBMITTED.
  
 D) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. ROOF MATERIAL IS NOT COMPOSITION
 SHINGLES. THIS IS A FLAT ROOF. SEE PLANS AND PRODUCT
 APPROVALS SUBMITTED AND REVISE AS REQUIRED.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME ENERGY
 CALCULATIONS WERE RE-SUBMITTED.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED AT TIME OF INSPECTION WHEN ENERGY
 CALCULATIONS ARE NOT USING THE DEFAULT FACTOR FOR
 GLAZING.
  
 4- FLAT ROOF NOA 14-1030.02 SUBMITTED.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
 REPEAT COMMENT. CALCULATIONS WERE REQUESTED ON PREVIOUS
 COMMENTS IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES. CALCULATIONS
 REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE NEW SCOPE OF WORK. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND ALL DESIGN PROFESSIONAL FEES. REVISE
 VALUATION AS REQUIRED. PROVIDE COPY OF PROPERLY SIGNED
 CONTRACT FOR BUILDING OFFICIAL REVIEW/APPROVAL. NOTE:
 INCLUDE THE DESIGN PROFESSIONAL FEES.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 6- ROOF TYPE SHOWN ON THE EXTERIOR ELEVATIONS ON NEW
 SHEET E-1 DON'T MATCH ROOF TYPE SHOWN ON THE PROPOSED
 ROOF PLAN ON SHEET A-1. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 7- STAIRS SHOWN ON THE NORTH ELEVATION, EAST ELEVATION
 ON SHEET E-1 AND GROUND FLOOR PLAN, SECOND FLOOR PLAN
 ON SHEET A-1 DON'T MAKE SENSE. NUMBER OF STEPS SHOWN
 AND THE WAY THEY ARE DRAWN DON'T MAKE ANY SENSE. THEY
 ARE NOT PROPERLY DRAWN. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 8- SCOPE OF WORK ON SHEET A-1 SPECIFIES "SAWCUT FLOOR
 FOR NEW FOOTING REQUIRED". PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THIS SCOPE OF WORK. SEC. R301.1
 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL. SAME DRAWING WAS
 RE-SUBMITTED.
  
 9- NEW REVISED COVER DRAWING: SIZE OF WINDOW #11 SHOWN
 ON THE EXISTING WINDOWS SCHEDULE, REPLACEMENT WINDOWS
 SCHEDULE AND SECOND FLOOR PLAN DON'T MATCH. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  