2016-08-23 15:32:24 | RESIDENTIAL (R3) ALTERATION, SIXTH BUILDING REVIEW |
| CHECKLIST. (REAR BUILDING). |
| CODE: FBC-5TH EDITION (2014). |
| |
| ****NOTE: SCOPE OF WORK WAS COMPLETELY REVISED. |
| |
| 1- INFORMATION SUBMITTED IN THE DESIGN CRITERIA IS NOT |
| CLEAR. CLARIFY WHAT IS THE EXTERNAL = -0.9, INTERNAL - |
| 0.2 AND NET UPLIFT COEFFICIENT=1.1 AND WHERE WERE ARE |
| THEM TAKEN FROM. ALSO, CLEARLY SPECIFY IF THE WIND LOAD |
| SPECIFIED IS THE ULTIMATE WIND LOAD OR NOMINAL WIND |
| LOAD. SEC. 107.2.1 CITY AMENDMENTS AND SEC. R301.1 |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| NEW BELL FOOTING SPECIFIED ON THE GROUND FLOOR PLAN. |
| CLEARLY SPECIFY WHAT'S THE PURPOSE OF THIS FOOTING. |
| WHAT IS IT REINFORCING? SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 3- ROOF FRAMING PLAN SPECIFIES EMBEDDED STRAP OR |
| SIMPSON MSTM16. THERE IS THE OPTION TO USE EITHER THE |
| EXISTING STRAP OR TO INSTALL A NEW ONE. CLEARLY SPECIFY |
| EXISTING STRAP TO VERIFY IF THE STRAP WILL MEET THE |
| DESIGN PRESSURES REQUIRED FOR ON CURRENT CODE. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| NOTE: IT LOOKS LIKE THERE IS A TYPO ON THE SPECIFIED |
| STRAP. DO YOU MEAN MTSM16?. REVISE AS REQUIRED. |
| |
| 4- SIZE OF SECOND FLOOR BEDROOM EGRESS WINDOW IS NOT |
| CLEAR. LEGEND CALLS EXISTING WINDOW #11 AS 52"X50 |
| JALOUSIE WINDOW; REPLACEMENT WINDOW #11 AS 52" X 53 |
| 5/8" IMPACT EGRESS WINDOW; WHILE SECOND FLOOR PLAN |
| CALLS WINDOW #11 AS 36X 53 5/8" EGRESS. REVISE AS |
| REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 5- SEC. R303.9 REQUIRES HEATING. PROVIDE INFORMATION |
| SHOWING HOW COMPLYING WITH THE HEAT REQUIREMENTS. PLANS |
| DON'T SHOW LOCATION OF THE PROPOSED HEATING UNIT. |
| |
| 6- DETAIL "C" ON SHEET A-2. SPECIFY SIZE OF EXISTING |
| FOOTING. CLARIFY HOW THE ENGINEER KNOWS THAT EXISTING |
| FOOTING IS ADEQUATE FOR THE NEW PROPOSED CONCENTRATED |
| LOAD. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 7- TWO STORY WALL SECTION ON SHEET A-2: |
| A) REVISE ROOF SHEATHING FASTENING TYPE AND SPACING. |
| SEE SEC. R803. 2.3.1 FBC-RESIDENTIAL AND REVISE AS |
| REQUIRED. |
| |
| B) REVISE ROOF FRAMING STRAPS. SEE ITEM # 3 ABOVE. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| C) THERE ARE NO SPECIFICATIONS FOR THE THE SECOND FLOOR |
| MATERIALS (SUBFLOORING AND FINISH FLOORING). SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| D) THERE ARE NO SPECIFICATIONS FOR ROOF, WALL AND |
| SECOND FLOOR INSULATION. COORDINATE WITH THE ENERGY |
| CALCULATIONS SUBMITTED. SEC. R103.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| E) GARAGE CEILING SPECIFICATIONS DON'T MATCH |
| SPECIFICATIONS SHOWN ON THE GROUND FLOOR ON SHEET A-1. |
| SEC. R302.1 FBC-RESIDENTIAL. |
| |
| F) CLARIFY HOW THE SPECIFIED ROOF VENTILATION PROVIDE |
| CROSS VENTILATION TO ENTIRE ROOF AS REQUIRED BY SEC. |
| R806 FBC-RESIDENTIAL. |
| |
| 8- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) NEED TO PROVIDE THE NAME OF THE PERSON RESPONSIBLE |
| FOR THE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| B) ENERGY CALCULATIONS SUBMITTED FORM 405-10 ARE FOR |
| THE 2010 CODE. THE CURRENT CODE IS FBC-5TH EDITION |
| (2014). NEED TO PROVIDE CURRENT FORM 405-2014. SEC. 553 |
| FLORIDA STATUTE. |
| |
| C) CEILING INSULATION ITEM #10. NEW PLANS CALL FOR 2 X |
| 8 ROOF JOISTS. R30 BATT INSULATION DOESN'T FIT ON A 2 X |
| 8 SPACE. BATT INSULATION IS +/- 9-1/2" THICK. IN |
| ADDITION WILL NEED AT LEAST 1" CLEAR SPACE FOR CROSS |
| VENTILATION. REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| D) SIZE OF A/C UNIT SHOWN ON ITEM #12 SEEMS TO BE TOO |
| LARGE FOR THE SIZE OF THE APARTMENT. THIS ITEM NEEDS TO |
| BE COORDINATED WITH THE A/C EQUIPMENT SIZING |
| CALCULATIONS. SEC. R403.6.1 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| F) PROVIDE COMPLETE INFORMATION FOR THE NEW ELECTRIC |
| WATER HEATER ITEM #14. SPECIFY SIZE AND EFFICIENCY. |
| SEC. R403.4.4 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| G) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 DOESN'T MATCH |
| PLANS. REVISE AS REQUIRED. NOTE: GRAVEL IS NOT ALLOWED. |
| SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| H) THE ATTIC VENT RATIO SHOWN ON PAGE 2 OF 5 IS 1/300. |
| SEC. R806.2 REQUIRES 1/150 RATIO. REVISE AS REQUIRED OR |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWN |
| COMPLIANCE WITH THE EXCEPTION OF SEC. R806.2. |
| |
| I) WINDOWS AREA AND ORIENTATION SHOWING ON PAGE 3 OF 5 |
| DOESN'T MATCH ACTUAL WINDOW AREA AND ORIENTATION SHOWN |
| ON PLANS. REVISE AS REQUIRED TO MATCH. SEC. R103.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| NOTE: |
| LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE |
| DEFAULT FACTOR FOR GLAZING. |
| |
| 9- PROVIDE DETAIL AND SPECIFICATIONS FOR THE CONCRETE |
| BLOCK WALL INSULATION R VALUE SPECIFIED ON THE ENERGY |
| CALCULATIONS. COORDINATE WITH ENERGY CALCULATIONS. SEC. |
| R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| HOW OBTAINING THE R8 VALUE ON THE DUCTS AS SPECIFIED ON |
| ITEM #11 OF THE ENERGY CALCULATIONS. SEC. R103.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| 11- PROVIDE PRODUCT APPROVAL ( 2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) NEW FLAT ROOF AS SPECIFIED ON PLANS. AND CLEARLY |
| MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| TO VERIFY THE DESIGN PRESSURES OF SEC. R301.1 |
| FBC-RESIDENTIAL. |
| NOTE: IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS |
| WILL BE REQUIRED. SEE LIMITATIONS ON PRODUCT APPROVAL. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH |
| SPECIFIED CONNECTOR. |
| |
| 12- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE |
| PRODUCT APPROVAL PRIOR TO SUBMITTAL AS REQUIRED BY SEC. |
| 107.3.4.1 CITY AMENDMENTS. |
| |
| 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW BASED ON ALL THE NEW SCOPE OF WORK. VALUATION TO |
| INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| PROFIT AND ALL DESIGN PROFESSIONAL FEES. REVISE |
| VALUATION AS REQUIRED. A COPY OF PROPERLY SIGNED |
| CONTRACT MAY BE SUBMITTED FOR BUILDING OFFICIAL |
| REVIEW/APPROVAL. NOTE: INCLUDE THE DESIGN PROFESSIONAL |
| FEES. |
| |
| NOTE: ON JUNE 23RD I MET WITH DANIEL MOSS (ENGINEER) TO |
| GO OVER THE COMMENTS FROM PREVIOUS CHECKLISTS. INFORMED |
| HIM ABOUT DRAFTSMAN'S DEFICIENCIES IN DRAWINGS. |
| |