2016-08-23 15:32:24RESIDENTIAL (R3) ALTERATION, SIXTH BUILDING REVIEW
 CHECKLIST. (REAR BUILDING).
 CODE: FBC-5TH EDITION (2014).
  
 ****NOTE: SCOPE OF WORK WAS COMPLETELY REVISED.
  
 1- INFORMATION SUBMITTED IN THE DESIGN CRITERIA IS NOT
 CLEAR. CLARIFY WHAT IS THE EXTERNAL = -0.9, INTERNAL -
 0.2 AND NET UPLIFT COEFFICIENT=1.1 AND WHERE WERE ARE
 THEM TAKEN FROM. ALSO, CLEARLY SPECIFY IF THE WIND LOAD
 SPECIFIED IS THE ULTIMATE WIND LOAD OR NOMINAL WIND
 LOAD. SEC. 107.2.1 CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW BELL FOOTING SPECIFIED ON THE GROUND FLOOR PLAN.
 CLEARLY SPECIFY WHAT'S THE PURPOSE OF THIS FOOTING.
 WHAT IS IT REINFORCING? SEC. R301.1 FBC-RESIDENTIAL.
  
 3- ROOF FRAMING PLAN SPECIFIES EMBEDDED STRAP OR
 SIMPSON MSTM16. THERE IS THE OPTION TO USE EITHER THE
 EXISTING STRAP OR TO INSTALL A NEW ONE. CLEARLY SPECIFY
 EXISTING STRAP TO VERIFY IF THE STRAP WILL MEET THE
 DESIGN PRESSURES REQUIRED FOR ON CURRENT CODE. SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IT LOOKS LIKE THERE IS A TYPO ON THE SPECIFIED
 STRAP. DO YOU MEAN MTSM16?. REVISE AS REQUIRED.
  
 4- SIZE OF SECOND FLOOR BEDROOM EGRESS WINDOW IS NOT
 CLEAR. LEGEND CALLS EXISTING WINDOW #11 AS 52"X50
 JALOUSIE WINDOW; REPLACEMENT WINDOW #11 AS 52" X 53
 5/8" IMPACT EGRESS WINDOW; WHILE SECOND FLOOR PLAN
 CALLS WINDOW #11 AS 36X 53 5/8" EGRESS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- SEC. R303.9 REQUIRES HEATING. PROVIDE INFORMATION
 SHOWING HOW COMPLYING WITH THE HEAT REQUIREMENTS. PLANS
 DON'T SHOW LOCATION OF THE PROPOSED HEATING UNIT.
  
 6- DETAIL "C" ON SHEET A-2. SPECIFY SIZE OF EXISTING
 FOOTING. CLARIFY HOW THE ENGINEER KNOWS THAT EXISTING
 FOOTING IS ADEQUATE FOR THE NEW PROPOSED CONCENTRATED
 LOAD. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- TWO STORY WALL SECTION ON SHEET A-2:
 A) REVISE ROOF SHEATHING FASTENING TYPE AND SPACING.
 SEE SEC. R803. 2.3.1 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED.
  
 B) REVISE ROOF FRAMING STRAPS. SEE ITEM # 3 ABOVE. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 C) THERE ARE NO SPECIFICATIONS FOR THE THE SECOND FLOOR
 MATERIALS (SUBFLOORING AND FINISH FLOORING). SEC.
 R301.1 FBC-RESIDENTIAL.
  
 D) THERE ARE NO SPECIFICATIONS FOR ROOF, WALL AND
 SECOND FLOOR INSULATION. COORDINATE WITH THE ENERGY
 CALCULATIONS SUBMITTED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) GARAGE CEILING SPECIFICATIONS DON'T MATCH
 SPECIFICATIONS SHOWN ON THE GROUND FLOOR ON SHEET A-1.
 SEC. R302.1 FBC-RESIDENTIAL.
  
 F) CLARIFY HOW THE SPECIFIED ROOF VENTILATION PROVIDE
 CROSS VENTILATION TO ENTIRE ROOF AS REQUIRED BY SEC.
 R806 FBC-RESIDENTIAL.
  
 8- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) NEED TO PROVIDE THE NAME OF THE PERSON RESPONSIBLE
 FOR THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) ENERGY CALCULATIONS SUBMITTED FORM 405-10 ARE FOR
 THE 2010 CODE. THE CURRENT CODE IS FBC-5TH EDITION
 (2014). NEED TO PROVIDE CURRENT FORM 405-2014. SEC. 553
 FLORIDA STATUTE.
  
 C) CEILING INSULATION ITEM #10. NEW PLANS CALL FOR 2 X
 8 ROOF JOISTS. R30 BATT INSULATION DOESN'T FIT ON A 2 X
 8 SPACE. BATT INSULATION IS +/- 9-1/2" THICK. IN
 ADDITION WILL NEED AT LEAST 1" CLEAR SPACE FOR CROSS
 VENTILATION. REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) SIZE OF A/C UNIT SHOWN ON ITEM #12 SEEMS TO BE TOO
 LARGE FOR THE SIZE OF THE APARTMENT. THIS ITEM NEEDS TO
 BE COORDINATED WITH THE A/C EQUIPMENT SIZING
 CALCULATIONS. SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 F) PROVIDE COMPLETE INFORMATION FOR THE NEW ELECTRIC
 WATER HEATER ITEM #14. SPECIFY SIZE AND EFFICIENCY.
 SEC. R403.4.4 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. NOTE: GRAVEL IS NOT ALLOWED.
 SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 H) THE ATTIC VENT RATIO SHOWN ON PAGE 2 OF 5 IS 1/300.
 SEC. R806.2 REQUIRES 1/150 RATIO. REVISE AS REQUIRED OR
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWN
 COMPLIANCE WITH THE EXCEPTION OF SEC. R806.2.
  
 I) WINDOWS AREA AND ORIENTATION SHOWING ON PAGE 3 OF 5
 DOESN'T MATCH ACTUAL WINDOW AREA AND ORIENTATION SHOWN
 ON PLANS. REVISE AS REQUIRED TO MATCH. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE
 DEFAULT FACTOR FOR GLAZING.
  
 9- PROVIDE DETAIL AND SPECIFICATIONS FOR THE CONCRETE
 BLOCK WALL INSULATION R VALUE SPECIFIED ON THE ENERGY
 CALCULATIONS. COORDINATE WITH ENERGY CALCULATIONS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW OBTAINING THE R8 VALUE ON THE DUCTS AS SPECIFIED ON
 ITEM #11 OF THE ENERGY CALCULATIONS. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 11- PROVIDE PRODUCT APPROVAL ( 2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW FLAT ROOF AS SPECIFIED ON PLANS. AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS
 WILL BE REQUIRED. SEE LIMITATIONS ON PRODUCT APPROVAL.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVAL PRIOR TO SUBMITTAL AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE NEW SCOPE OF WORK. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND ALL DESIGN PROFESSIONAL FEES. REVISE
 VALUATION AS REQUIRED. A COPY OF PROPERLY SIGNED
 CONTRACT MAY BE SUBMITTED FOR BUILDING OFFICIAL
 REVIEW/APPROVAL. NOTE: INCLUDE THE DESIGN PROFESSIONAL
 FEES.
  
 NOTE: ON JUNE 23RD I MET WITH DANIEL MOSS (ENGINEER) TO
 GO OVER THE COMMENTS FROM PREVIOUS CHECKLISTS. INFORMED
 HIM ABOUT DRAFTSMAN'S DEFICIENCIES IN DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT