2016-08-24 16:16:17 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: |
| JOB ADDRESS: 354 MARLBORO PL. REAR |
| DESCRIPTION: INTERIOR RENOVATIONS OF REAR BLDG. |
| MASTER PERMIT: 15070952 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. CORRECT THE TITLE BLOCK TO INCLUDE THE ELECTRICAL |
| WORK. ACCORDING TO THE EXISTING TITLE BLOCK, NO |
| ELECTRICAL WORK IS TO BE DONE. |
| 2. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE FPL |
| UTILITY POLE AND SERVICE DROP TO THE METER. INCLUDE THE |
| MAIN SERVICE DISCONNECT. |
| 3. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS |
| ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED. |
| THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND |
| INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE |
| SPECIFIC. |
| 4. FBC-RE E3705.8/NEC240.24(B): READY ACCESS FOR |
| OCCUPANTS. EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL |
| OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING |
| THAT OCCUPANCY. THE SUBMITTED DRAWINGS SHOW THE |
| ELECTRICAL PANEL IN THE GARAGE WITH NO DIRECT ACCESS TO |
| THE UPPER BLDG. |
| 5. FBC-RE 3903.3/NEC 210.70: ILLUMINATION FOR THE |
| STAIRWAY IS REQUIRED. FURTHERMORE, THE STAIRWAY |
| LIGHTING SHALL BE CONTROLLED FROM BOTH TOP AND BOTTOM |
| UNLESS AUTOMATIC CONTROL IS INSTALLED. |
| 6. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE A |
| PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING |
| THE SPECIFIC PURPOSE OF EVERY CIRCUIT. |
| 7. E3601.6.2: SERVICE DISCONNECT LOCATION. THE SERVICE |
| DISCONNECTING MEANS SHALL BE INSTALLED AT A READILY |
| ACCESSIBLE LOCATION EITHER OUTSIDE OF A BUILDING OR |
| INSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE |
| CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL NOT BE |
| INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE ACCESS |
| TO THE DISCONNECT SERVING THE DWELLING UNIT IN WHICH |
| THEY RESIDE. INDICATE IF THE PANEL IS MAIN LUG ONLY OR |
| MAIN BREAKER. |
| 8. R404.1: LIGHTING EQUIPMENT (MANDATORY). A MINIMUM OF |
| 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED |
| LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED |
| LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY |
| LAMPS. |
| 9. R303.9: REQUIRED HEATING. WHEN THE WINTER DESIGN |
| TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C), |
| EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING |
| FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM |
| TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM) |
| ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS |
| IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE |
| INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS |
| SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS |
| SECTION. THEREFORE HEAT SHALL BE PROVIDED FOR FINAL |
| INSPECTION. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |
2016-08-24 10:35:25 | NEW REVISED DRAWINGS SUBMITTED |