2016-04-06 17:49:43 | RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW |
| CHECKLIST. (REAR BUILDING). |
| CODE: FBC-5TH EDITION (2014). |
| |
| *****NOTE: ACCORDING TO FLORIDA STATUTE 553.80(2)(B) |
| ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| REVIEW FEE EACH TIME AFTER THE THIRD REVIEW. |
| |
| |
| 1- PLANS SHOW NEW OPENINGS FOR GARAGE OVERHEAD DOORS. |
| PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR |
| THE NEW GARAGE DOORS. SPECIFY REINFORCEMENT AT THE ENDS |
| OF EACH OPENING. SPECIFY LINTEL OR BEAM, SPECIFY |
| STRUCTURAL BUCK ATTACHMENT, ETC. SEC. R301 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| RESPONSE: A) DETAIL SUBMITTED DOESN'T PROVIDE ANY |
| STRUCTURAL SPECIFICATIONS FOR THE REINFORCEMENT AT THE |
| ENDS OF EACH OPENING. THERE ARE NO SPECIFICATIONS |
| SHOWING HOW THE EXISTING MASONRY WALLS ARE REINFORCED |
| TO RECEIVE THE LOADS OF THE NEW GARAGE DOORS. |
| |
| B) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 1/2 |
| ANCHOR BOLTS SPECIFIED ON THE GARAGE DOOR BUCK DETAIL. |
| SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| NOTE: ONLY THE FRONT BUILDING IS CONTRIBUTING HISTORIC |
| BUILDING. THE REAR BUILDING IS NOT. THEREFORE, IT'S NOT |
| EXEMPT FROM THE ENERGY CODE. |
| |
| RESPONSE: RESPONSE LETTER STATES "A/C & HEAT UNDER |
| SEPARATE PERMIT W/ ENERGY CALCULATIONS". THIS DOESN'T |
| ADDRESS THE COMMENT. ENERGY CALCULATIONS AND A/C & HEAT |
| CALCULATIONS ARE TWO DIFFERENT THINGS. THE INFORMATION |
| FOR THE A/C & HEAT CALCULATIONS ALONG WITH THE A/C |
| PLANS MAY BE SUBMITTED UNDER A SEPARATE PERMIT BUT THE |
| ENERGY CALCULATIONS NEED TO BE SUBMITTED NOW. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| DWELLING/GARAGE FIRE SEPARATION AS REQUIRED BY SEC. |
| R302.6 OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| |
| RESPONSE: SPECIFICATIONS ON PLANS DOESN'T SPECIFY THE |
| TYPE OF GYPSUM WALL BOARD AS REQUIRED BY TABLE R302.6 |
| OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| |
| ****ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| ADDRESSING EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |