2016-02-16 16:43:56 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW |
| CHECKLIST. (REAR BUILDING). |
| CODE: FBC-5TH EDITION (2014). |
| |
| NOTE: |
| PLANS WERE REVISED. NEW SCOPE OF WORK IS SHOWN. |
| COMMENTS BELOW ARE BASED ON THE NEW PLANS PROVIDED. |
| |
| 1- VALUATION DECLARED IN THE PERMIT APPLICATION. REVISE |
| VALUATION TO INCLUDE ALL THE SCOPE OF WORK SHOWN ON |
| PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. |
| |
| 2- PLANS SHOW NEW OPENINGS FOR GARAGE OVERHEAD DOORS. |
| PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR |
| THE NEW GARAGE DOORS. SPECIFY REINFORCEMENT AT THE ENDS |
| OF EACH OPENING. SPECIFY LINTEL OR BEAM, SPECIFY |
| STRUCTURAL BUCK ATTACHMENT, ETC. SEC. R301 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 3- ACCORDING TO NEW PLANS PROVIDED, THIS IS ALTERATION |
| LEVEL 3 NOT ALTERATION LEVEL 2. REVISE DESIGN CRITERIA |
| INFORMATION AS REQUIRED. SEC. 505 OF FBC-EXISTING |
| BUILDING, 5TH EDITION (2014). |
| |
| 4- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| NOTE: ONLY THE FRONT BUILDING IS CONTRIBUTING HISTORIC |
| BUILDING. THE REAR BUILDING IS NOT. THEREFORE, IT'S NOT |
| EXEMPT FROM THE ENERGY CODE. |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR THE INSWING DOOR SHOWN ON THE |
| FIRST FLOOR PLAN. |
| |
| 6- ENGINEER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| DWELLING/GARAGE FIRE SEPARATION AS REQUIRED BY SEC. |
| R302.6 OF FBC RESIDENTIAL, 5TH EDITION (2014). |
| |
| 8- PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE |
| HEATING REQUIREMENTS OF SEC. R303.9 OF FBC RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| 9- SHOW CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| SLEEPING ROOMS AS REQUIRED BY SEC. R315.1. NOTE: THERE |
| IS A NEW GARAGE BELOW THE DWELLING UNIT. |
| |
| ****ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER |
| ADDRESSING EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |