Plan Review Notes For Permit 15070952 |
Permit Number |
15070952 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-22 15:48:32 | 1ST REVIEW: FBC 2014 5TH ED. | | | | THERE ARE TWO APPLICATIONS ONE FOR A FRONT BUILDING AND | | ONE FOR A REAR BUILDING, BUT THE PLAN IS ONLY FOR ONE | | BUILDING. ACCORDINGLY, I CANNOT DETERMINE THE SCOPE OF | | WORK. | | | | THE APPLICABLE ELECTRICAL CODE IN THE A FUNCTION OF THE | | BASE CODE CITED ABOVE. PLEASE REVISE PLAN TO INDICATE | | THE APPLIED CODE IN EFFECT. | | | | A LOAD CALCULATION IS PROVIDED BUT IT IS UNKNOW IF IT | | APPLIES TO ONR OR BOTH BUILDINGS/ | | | | THE RANGE CUICUIT SHOWN IS 40AMP, PROVIDE APPLIANCE | | INFORMATION TO DEMONSTRATE ADEQUACY OF THIS OCP. | | E4101.4 OVERCURRENT PROTECTION. | | EACH APPLIANCE SHALL BE PROTECTED AGAINST OVERCURRENT | | IN ACCORDANCE WITH THE RATING OF THE APPLIANCE AND ITS | | LISTING. | | | | INFORMATION PROVIDE IS NOT SUFFICIENT TO ALLOW FOR FULL | | REVIEW. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] |
|