Plan Review Notes For Permit 15070928 |
Permit Number |
15070928 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-25 16:39:46 | 1ST REVIEW: FBC 2014 5TH ED. | | | | IT IS ASSUMED THIS IS AN AREA PREVIOUSLY NOT | | CONDITIONED. PROVIDE EVIDENCE OF EXISTING PERMITTED | | HVAC WORK OR THE BELOW WILL APPLY: | | | | FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW | | SUPPLY DUCTS PER FBC-R M16 & EQUIPMENT | | | | FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION. | | | | FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT BEDROOMS. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|