Date |
Text |
2015-08-25 16:07:46 | 1ST REVIEW: FBC 2014 5TH ED. |
| |
| FROM CITY RECORDS, IT CANNOT BE ASCERTAINED THAT THE |
| AREA DEPICTED ON THE PLAN SHOWN AS "AS BUILT" AND |
| INDICATED AS HABITAL SPACE CONSISTING OF A FAMILY ROOM, |
| TWO BEDROOMS, A LIVING ROOM AND LAUNDRY ROOM, WAS |
| PREVIOUSLY CONSTRUCTED FOR HABITAL USE WITHIN THE R3 |
| OCCUPANCY CLASSIFICATION. PERMIT 6365I WAS ISSUED ON |
| 6/1/1983, I PRESUME THAT IS WHEN THE APPROXIMATELY 650 |
| SF AREA WAS BUILT. THE PROPERTY APPRAISER WEB SITE |
| SHOWS THIS PORTION OF THE STRUCTURE AS "SEMI FINISHED |
| BASE AREA." |
| |
| PLEASE PROVIDE ANY RECORDS YOU MAY HAVE TO DEMONSTRATE |
| CONSTRUCTION DETAILS OF THIS PART OF THE STRUCTURE. |
| ALTERNATIEVLY, IF THE IMPROVEMENTS ARE AS COMPLETE AS |
| THE PLAN INDICATES, PROVIDE THE FOLLOWING: |
| |
| AN ENERGY SUBMITTAL |
| |
| FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| DETAILS TO DEMONSTRATE PROPOSED OR EXISTING BUILDING |
| ENVELOPE THERMAL EFFICIENTCY. |
| |
| FBC - R301.2.1.2 PROTECTION OF OPENINGS. PROVIDE AN |
| IMPACT PROTECTION SUBMITTAL. |
| WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS |
| REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM |
| WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR |
| WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE |
| LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12 |
| OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN. |
| |
| ADVISORY COMMENT IF WORK WAS COMPLETED WITHOUT A PERMIT |
| PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY |
| COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR |
| INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL |
| CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 |
| & FBC 117. |
| |
| FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A |
| PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| PURPOSES UNTIL APPROVED. |
| |
| FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| |
| |