Plan Review Notes For Permit 15070912 |
Permit Number |
15070912 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-30 13:47:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. SHEET A 1.01, INDICATES AN ENCLOSED STORAGE SPACE | | UNDER THE INTERIOR STAIRS. PROVIDE DOCUMENTATION/DETAIL | | CONFIRMING THE INSTALLATION OF 1 HOUR FIRE RATING UNDER | | THE STAIRS AND/OR THE EXISTANCE OR INSTALLATION OF FIRE | | SPRINKLER PROCTECTION UNDER THE STAIRS. | | | | 2. SHEET A 6.10, PROVIDE GREATER DETAIL/DRAWING OF THE | | STAIRWAY COMPLYING WITH NFPA 101, CHAPTER 7, 7.2.2.4, | | GUARDS AND HANDRAILS. |
|