Plan Review Notes
Plan Review Notes For Permit 15070821
Permit Number 15070821
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-27 13:42:10REVISION DENIED
 1) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL.
 2010 FBC (M)
 2) PROVIDE A DETAIL FROM THE ENGINEER ON THE SIZE
 AND TYPE BOLTS USED 310.12 WIND RESISTANCE
 2010 FBC (M)
 3) PLEASE SUBMIT A DETAIL SHOWING A WAY TO
 ANCHOR THE CONDENSERS WITH OUT THE STRAP GOING
 OVER THE TOP OF THE CONDENSER
 4) REFER TO TABLE 305.4 PIPING SUPPORTS SPACINGS
 2010 FBC (M)
 5) FRESH AIR MUST BE 10 FT FROM LOT LINE SECTION 401.4
 #1 2010 FBC (M)
 6) PLEASE PROVIDE A DETAIL FROM THE ENGINEER ON
 HOW THE PIPING SUPPORT WILL BE ANCHORED TO THE
 ROOF. 301.12 WIND RESISTANCE 2010 FBC (M)
 7) REFER TO SECTION 305.2 MATERIALS
 2010 FBC (M)
 8) REFER TO SECTION 304.11 GUARDS
 (EQUIPMENT AND ROOF HATCH)
 2020 FBC (M)
 9) KITCHEN HOOD AND GREASE DUCT REQUIRE
 SEPARATE PERMITS.
 10) PLEASE IDENTIFY THE PAGES ON THE PLAN
 ( 1ST FLOOR 2 FLOOR ) SECTION 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676