2015-07-20 10:07:40 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) PAGES 1-3 OF THE FLORIDA PRODUCT APPROVAL (FL5680 - |
| R15) ARE REQUIRED TO BE SUBMITTED. FBC 107.2.1 |
| |
| 2) SUBMIT TWO COPIES OF THE WITHDRAWL TESTING REQUIRED |
| BY NOTE #10 ON PAGE 2 OF THE PRODUCT APPROVAL. 10. FOR |
| MECHANICALLY ATTACHED COMPONENTS OVER EXISTING DECKS, |
| FASTENERS SHALL BE TESTED IN THE EXISTING DECK FOR |
| WITHDRAWAL RESISTANCE. A QUALIFIED DESIGN PROFESSIONAL |
| SHALL REVIEW THE DATA FOR COMPARISON TO THE MINIMUM |
| REQUIREMENTS FOR THE SYSTEM. TESTING AND ANALYSIS SHALL |
| BE IN ACCORDANCE WITH TAS 105 OR ANSI/SPRI FX-1. |
| |
| 3) SUBMIT TWO COPIES OF SIGNED AND SEALED ENHANCED |
| FASTENING CALCULATIONS FOR ROOF ZONES 2 AND 3 AS |
| REQUIRED BY NOTE # 8 ON PAGE 2 OF THE PRODUCT APPROVAL. |
| 8. FOR MECHANICALLY ATTACHED COMPONENTS OR PARTIALLY |
| BONDED INSULATION, THE MAXIMUM DESIGN PRESSURE FOR THE |
| SELECTED ASSEMBLY SHALL MEET OR EXCEED THE ZONE 1 |
| DESIGN PRESSURE DETERMINED IN ACCORDANCE WITH FBC |
| CHAPTER 16, AND ZONES 2 AND 3 SHALL EMPLOY AN |
| ATTACHMENT DENSITY DESIGNED BY A QUALIFIED DESIGN |
| PROFESSIONAL TO RESIST THE ELEVATED PRESSURE CRITERIA. |
| COMMONLY USED METHODS ARE RAS 117 AND FM LPDS 1-29. |
| ASSEMBLIES MARKED WITH AN ASTERISK* CARRY THE |
| LIMITATIONS SET FORTH IN SECTION 2.2.1.5.1(A) OF FM |
| LPDS 1-29 FOR ZONE 2/3 ENHANCEMENTS. |
| |
| 4) SUBMIT TWO COPIES OF A SIGNED AND SEALED ROOF |
| MOISTURE SURVEY. FBC 1510.3 |
| |
| 5) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING AND THE |
| NUMBER OF EXISTING ROOF COVERING SYSTEMS ALREADY IN |
| PLACE. FBC 1510.3 |
| |
| 6) THE VALUE FOR THE WORK APPEARS TO BE A LITTLE LOW. |
| SUBMIT A COPY OF THE SIGNED CONTRACT. FBC 109.3 |