2015-08-04 14:02:56 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 15070710 |
| W. P. B. PERMIT: 15060166 |
| ADD: 1450 CENTREPARK BLVD. SUITE 300 & 225 |
| CONT: CHANDLER CONSTRUCTION |
| TEL: (561)373-0297 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 04/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEET A2 & A5 SHOW A NEW COMMUNICATING STAIR BETWEEN |
| UNIT 225 & 300. PLEASE SHOW COMPLIANCE WITH THE 2010 |
| FBC-B 708.2 EXCEPTION 2.1 OR OTHER EXCEPTION THAT THE |
| NEW COMMUNICATING STAIR WAS DESIGN TO OR EXCEPTION. THE |
| 2007 FBC-B COMMENTARY 708.2 EXCEPTION 2.1 DOES PROVIDE |
| A FORMULA SHOWN, FIGURE 707.2(1) TO SHOW CODE |
| COMPLIANCE IN THE ALLOWABLE OPENING. |
| |
| 2) A2 & A5 THE PLANS ALSO FAIL TO SHOW COMPLIANCE WITH |
| THE USE OF A CURTAIN BOARD (DRAFT CURTAIN) AND CLOSELY |
| SPACED SPRINKLERS MAXIMUM 6'-0" O.C. AND 6 IN. -12 IN. |
| FROM THE DRAFT CURTAIN. SEE THE 2007FBC-B COMMENTARY |
| 708.2 EXCEPTION 2.1 SEE, FIGURE 707.2(1). |
| |
| 3) SHEET A5 INDICATES THE USE OF STAINED WOOD STAIR |
| STRINGERS, PLEASE PROVIDE WHAT THE MINIMUM BUILDING |
| TYPE IS FOR THIS BUILDING AND COMPLIANCE WITH 2010 |
| 1009.6. STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL BE |
| BUILT OF MATERIALS CONSISTENT WITH THE TYPES PERMITTED |
| FOR THE CONSTRUCTION OF THE BUILDING, EXCEPT THAT WOOD |
| HANDRAILS SHALL BE PERMITTED FOR ALL TYPES OF |
| CONSTRUCTION. |
| |
| 4) NEITHER A2 NOR SHEET A5 PROVIDE THE GUARDRAIL |
| DETAILS FOR THE GUARDRAIL OF THE UPPER 3RD FLOOR NOR |
| THE MID-LANDING. PLEASE SHOW COMPLIANCE WITH 2010 FBC-B |
| 1013.2, 1013.31013.4 & 1607.8.1. |
| |
| 5) PLEASE NOTE THIS IS A 3 STORY BUILDING AND WILL |
| QUALIFY FOR A RESIDENT INSPECTOR. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES. THE |
| BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY |
| OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE |
| MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| SERVICE IN THE FOLLOWING INSTANCES: |
| |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 |
| POUNDS PER SQUARE INCH |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION |
| |
| 5A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| DEPARTMENT. |
| |
| 5B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 5C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| [email protected] |
| |
| 5D) FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. |
| FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT |
| LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH |
| STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. |
| |
| 5E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |