Plan Review Notes
Plan Review Notes For Permit 15070620
Permit Number 15070620
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-16 16:26:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070620
 ADD: 701 S. OLIVE AVE. SUITE # 1023
 CONT: COMPLETE SOLUTIONS USA
 TEL: ( 561)337-7793
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 7/16/2015
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES TO INSTALL FLOOR
 SOUND PROOFING AND WOOD FLOORS. THE SUBMITTED TEST
 REPORTS ARE FOR A 8 INCH SLAB, NOT VERIFIED, OVERLAID
 WITH:
 QUARRY TILE OVER PROFLEX 90 MEGA SOUND CONTROL MEMBRANE
 UNDERLAYMENT. THERE IS A DISCREPANCY IN THE SUBMITTED
 REPORT AND ACTUAL FINISH FLOOR. THE SUBMITTED REPORT IS
 TESTED WITH QUARRY TILE NOT WOOD FLOORING. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  