2015-07-17 16:10:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070555
  
 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW AC SYSTEM IN ACCORDANCE WITH ACCA MANUAL N OR
 THE ACCA/ASHRAE STANDARD 183- SECTION C403.2.1 FBC
 FIFTH EDITION 2014 ENERGY CONSERVATION CODE.
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED IN THE
 RETURN DUCT OF THE NEW AHU, AND THE RETURN DUCTS OF THE
 EXISTING AHU'S- REFER TO SECTIONS 606.2.1 & 606.2.2
 FBC- 2014 MECHANICAL. SHOW THE LOCATIONS OF THE DEVICES
 ON THE PLANS AND INDICATE HOW THEY WILL BE SUPERVISED
 PER SECTION 606.4.1.
 3) INDICATE THE TYPE AND DIAMETER OF THE CONDENSATE
 PIPE PER TABLE 307.2.2, AND PROVIDE DETAILS FOR
 SECONDARY DISPOSAL: A) PAN DIMENSIONS, DEPTH, AND GAGE
 OF STEEL. B) TYPE AND SIZE OF PAN DRAIN PIPE AND
 TERMINATION LOCATION- REFER TO SECTION 307.2.3 FOR
 ADDITIONAL INFORMATION.
 4) THE SCOPE OF WORK NOTE #1 ON THE CONTRACT INDICATES
 A 12X24 FT. MOUNTING PAD FOR THE CONDENSER, HOWEVER THE
 PLAN INDICATES A 4X34 FT. PAD: PLEASE CLARIFY AND
 PROVIDE STRUCTURAL DETAILS FOR THE PAD, AND WIND LOAD
 TIE DOWN ENGINEERING FOR MOUNTING THE CONDENSER TO THE
 PAD.
  