2015-09-14 18:06:08NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- BRING PLANS TO PBC FOR IMPACT FEES ASSESSMENT.
  
 2- SHEET D-1: REVISE DRAINAGE NOTE. THIS HOUSE IS NO
 LOCATED ON EDMOR RD. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SHEET A-1:
 A) PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING
 TO THE DINING ROOM AREA. THIS DOORS NEEDS TO BE SELF
 CLOSING AS REQUIRED BY SEC. R302.5.1 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) SPECIFY SIZE OF ATTIC ACCESS. NOTE: LOCATION OF
 ATTIC ACCESS LOCATED IN THE GARAGE TO PROVIDE CLEAR
 HEADROOM OF 30" AS REQUIRED BY SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 ALSO, NEED TO SPECIFY ATTIC ACCESS BY REAR FAMILY ROOM
 WING AND MASTER BEDROOM WING AS REQUIRED BY SEC. R807
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- SHEET A-2: SPECIFY SIZE OF ATTIC ACCESS. NOTE:
 LOCATION OF ATTIC ACCESS TO PROVIDE CLEAR HEADROOM OF
 30" AS REQUIRED BY SEC. R807 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 5- SHEET A-5:
 A) OPENING SIZE SHOWN FOR THE ATTIC ACCESS DETAIL
 DOESN'T COMPLY WITH SEC. R807.1 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE AS REQUIRED.
  
 B) PROVIDE SPECIFICATIONS FOR FIREBLOCKING UNDER
 STAIRWAY AS REQUIRED BY SEC. R302.11 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) DIMENSIONS SHOWN ON THE EGRESS DIAGRAM ARE NOT
 LEGIBLE. THEY ARE TOO SMALL. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 6- GUARDRAILS SHOWN ON SECOND FLOOR BALCONY DON'T
 COMPLY WITH THE OPENINGS LIMITATIONS OF SEC. R312 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE COMPLETE
 DETAIL OF PROPOSED GUARDRAIL SHOWING COMPLIANCE.
  
 7- GEOTECHNICAL ENGINEERING REPORT RECOMMENDS SHALLOW
 FOUNDATIONS AT LEAST 18" EMBEDMENT BELOW LOWEST
 FINISHED SURROUNDING GRADE. SIZE OF FOOTINGS SHOWN ON
 THE STRUCTURAL DRAWINGS PROVIDE ONLY 12" EMBEDMENT.
 DESIGNER OF RECORD TO ADDRESS THIS ISSUE. EXPLAIN IF
 FOLLOWING GEOTECHNICAL REPORT RECOMMENDATIONS OR NOT. .
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 8- ENERGY CALCULATIONS SUBMITTED (COORDINATE PLANS AND
 ENERGY CALCULATIONS TO AVOID CONFLICTS OR DELAYS):
  
 A) PROVIDE CURRENT FORM. THE CURRENT CODE IS THE 2014
 CODE NOT 2010..
  
 B) PLANS SHOW UNVENTED ATTIC, WHILE ENERGY CALCULATIONS
 SHOW VENTED ATTIC. REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) CLEARLY IDENTIFY WHICH ARE THE INSULATED DOORS
 SPECIFIED ON PAGE 4 OF 7. SEE PRODUCT APPROVALS
 SUBMITTED. ALSO, CHECK ORIENTATION OF DOOR. SEC. R103.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) PROVIDE THE NAME OF THE BUILDER ON TOP OF THE FORM.
  
 9- COORDINATE PLANS AND ENERGY CALCULATIONS. PLANS TO
 SHOW INSULATION ON ALL WALLS AND CEILINGS TO MATCH
 ENERGY CALCULATIONS. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 10- DOORS ON THE EXTERIOR OPENING SCHEDULE (SHEET A-1
 AND A-2) DON'T MATCH EXTERIOR ELEVATIONS AND PRODUCT
 APPROVALS SUBMITTED. FOR EXAMPLE SEE CABANA BATH, ENTRY
 DOOR AND GARAGE DOOR. REVISE AS REQUIRED TO MATCH. AND
 CLEARLY MARK ON EACH PRODUCT APPROVAL ENTRY DOOR,
 CABANA BATH DOOR AND GARAGE DOOR. THIS IS WHY THERE IS
 A CONFLICT ON THE ENERGY CALCULATIONS ALSO. SEC. R103.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 11- PROVIDE COMPLETE SPECIFICATIONS FOR THE FLOORING OF
 THE BALCONY. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA
 13-0321.07 SUBMITTED IS FOR 4", 6" AND 12" LINTELS.
 THIS IS NOT THE SIZE SPECIFIED ON PLANS.
  
 B) GARAGE OVERHEAD DOOR. FLORIDA PRODUCT APPROVAL
 SUBMITTED IS FOR 2010 CODE. NEED CURRENT 2014 CODE
 VERSION.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS. FLORIDA PRODUCT
 APPROVALS SUBMITTED ARE FOR 2010 CODE. NEED CURRENT
 2014 CODE VERSION.
  
 D) FIBERGLASS EXTERIOR DOOR. FLORIDA PRODUCT APPROVAL
 SUBMITTED IS FOR 2010 CODE. NEED CURRENT 2014 CODE
 VERSION.
  
 E) UNDERLAYMENT SPECIFIED FOR THE BALCONY FLOORING.
 COORDINATE WITH ITEM #11 ABOVE.
  
 F) COLONIAL SHUTTERS AS SHOWN ON PLANS. AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE.
  
 13- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 ATTACHMENT OF THE ALUMINUM LOUVERS SHOWN ON THE REAR
 EXTERIOR ELEVATION. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  