2015-09-21 11:17:12 | 2ND REVIEW: FBC 2014 5TH ED. |
| |
| APPARENTLY CHANGES WERE MADE TO THE ORIGINAL PLAN AS A |
| FUNCTION OF THE HISTORIC REVIEW AS TO RETAINING THE |
| CARRIAGE DOORS. THE CHANGES, ALONG WITH THE ASSOCIATED |
| PRODUCT APPROVALS FOR THE WINDOWS AND DOORS MUST BE |
| REVIEWED BY THE DESIGNER OF RECORD. STEPHEN GAYDOSH. |
| (NOTE, THE RE-SUBMITTED PLAN IS NOT CONSISTENT WITH THE |
| PREVIOUS PLAN APPROVED BY THE HISTORIC PLANNER. |
| |
| INDICATE IF THE BUILDING IS EXEMPT FROM THE |
| REQUIREMENTS OF THE FBC ENERGY CONSERVATION. IF NOT, |
| PROVIDE EITHER: |
| |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| R303.9 REQUIRED HEATING. |
| WHEN THE WINTER DESIGN TEMPERATURE IN TABLE R301.2(1) |
| IS BELOW 60?F (16?C), EVERY DWELLING UNIT SHALL BE |
| PROVIDED WITH HEATING FACILITIES CAPABLE OF MAINTAINING |
| A MINIMUM ROOM TEMPERATURE OF 68?F (20?C) AT A POINT 3 |
| FEET (914 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM |
| EXTERIOR WALLS IN ALL HABITABLE ROOMS AT THE DESIGN |
| TEMPERATURE. THE INSTALLATION OF ONE OR MORE PORTABLE |
| SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE |
| WITH THIS SECTION. |
| |
| |