Plan Review Notes
Plan Review Notes For Permit 15070534
Permit Number 15070534
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-31 09:29:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070534
 ADD: 4117 BROADWAY
 CONT: DREAMWORKS CONST. & REMOD.
 TEL: (813)249-5541
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 31/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THE WIND DESIGN CRITERIA AS
 169 VULT, EXPOSURE C, THE POSITIVE AND NEGATIVE
 PRESSURES ARE IN VULT WITH THE EXCEPTION OF ROOF ZONE #
 3, ZONE 3 PRESSURES ARE IN VASD. PLEASE SUBMIT ALL
 PRESSURES IN VASD SINCE ALL PRODUCT APPROVALS ARE IN
 VASD.
 2014 FBC-B 1609.3.1.
  
 2) THE COVERSHEET LIST VARIOUS PRODUCT APPROVALS.
 PLEASE SUBMIT THE ACTUAL PRODUCT APPROVALS FOR REVIEW
 FOR CODE COMPLIANCE.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. NOTE ALL GLAZING SIZES, TYPE OF
 GLAZING, FASTENERS AND PRESSURES
 (B) WINDOWS NOTE ALL GLAZING SIZES, TYPE OF GLAZING,
 FASTENERS AND PRESSURES
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, NOTE ALL GLAZING SIZES, TYPE OF
 GLAZING, FASTENERS AND PRESSURES
 (D) ROOFING PRODUCTS AND ASSEMBLIES, IDENTIFY WHICH
 SUB-SYSTEM TO BE INSTALLED, IF LIMITATION # 7 ENHANCED
 FASTENING, BY DESIGN PREFESSIONAL,
 PROVIDE RAS 117 CALCULATIONS.
 (G) PRE-ENGINEERED A/C STANDS
  
 3) SHEET SP1-SP6: PROVIDE CURRENT PRODUCT APPROVALS
 REVIEWED BY THE DESIGNER OF RECORD.
 NOA 08-0715.03 09/11/2013 EXPIRED
 NOA 09-0127.13 03/04/2014 EXPIRED
  
 3A) SHEET A-2 INDICATES THE STOREFRONT GLAZYING SYSTEM
 IS TO BE ALUMINUM FRAME, DOUBLE PIAN INSULATED CLEAR
 TEMPERED IMPACT RESISTANT GLAZING. THE PRODUCT APPROVAL
 TO BE SUBMITTED MUST MEET ALL OF THESE COMPONENTS,
  
 4) 2014 FBC-ENERGY CODE PLEASE REVIEW C101.4.8
 EXCEPTIONS RENOVATED BUILDINGS MUST MEET THE 2014
 FBC-COMMERCIAL ENERGY. SEE DEFINITION OF RENOVATED
 BUILDING.
  
 2014 FBC-ENERGY DEFINITIONS: RENOVATED BUILDING. A
 RESIDENTIAL OR NON-RESIDENTIAL BUILDING UNDERGOING
 ALTERATIONS THAT VARIES OR CHANGES INSULATION, HVAC
 SYSTEMS, WATER HEATER SYSTEMS OR, EXTERIOR ENVELOPE
 CONDITIONS, PROVIDED THE ESTIMATED COST OF RENOVATION
 EXCEEDS 30 % OF THE ASSESSED VALUE OF THE STRUCTURE.
 THE P. B. C. PROPERTY APPRAISERS OFFICE HAS THE VALUE
 OF THE STRUCTURE LISTED AT $64,656.00 AND THE VALUE OF
 THE PERMIT APPLICATION IS LISTED AT $100,000.00.
  
 THE DESIGNER OF RECORD SHALL PROVIDE COMPLIANCE FOR THE
 2014 FBC-COMMERCIAL ENERGY C401.2 THROUGH EITHER THE
 PRESCRIPTIVE REQUIREMENTS OR BY C407 PREFORMANCE BASED
 TOTAL BUILDING PREFORMANCE BASED CALCULATIONS.
  
 5) 2014 FBC-ACCESSIBILITY CODE SECTION 202.4.2
 DISPROPORTIONATE COST . ACCESSIBLE FEATURES IN THE
 EVENT OF DISPROPORTIONATE COST. THE CONTRACT VALUE OF
 THIS PROJECT IS $100,000.00 DOLLORS DISPROPORTION COST
 ARE AT 20 % OF THE PROJECT OR $20,000.00 FOR ACCESIBLE
 UPGRADES. THE FUNDS ARE TO BE SPENT ONACCESSIBLE
 ELEMENTS FOR ACCESSIBLE ENTRANCES (NO STEPS, RAMPS
 ENTRANCES), AN ACCESSIBLE ROUTE, ACCESSIBLE
 RESTROOMSDRINKING FOUNTAINS. EITHER THE CONTRACTOR OR
 DESIGN PROFESSIONAL IS TO SUBMIT A ITEMIZED REPORT
 WHERE THESE MONIES WILL BE SPENT.
  
 6) NOTE THE RESTROOMS DO NOT MEET THE 2010
 FBC-ACCESSIBLITY REQUIREMENTS, SEE 604.3.2 OVERLAP.
  
 7A) SHEET A-2 INDICATES THIS TO BE A PRE-ENGINEERED
 AWNING, BUT THERE IS NO WIND DESIGN CRITERIA, IS THIS
 AWNING ONE THAT CAN BE REPOSITIONED IN THE EVENT OF A
 HIGH WIND EVENT OR IS THIS A FIXED OPEN AWNING? SHEET
 A-3 SHOWS A DETAIL OF THE SAME AWNING THE NOTES DO NOT
 MENTION IF THERE IS A SUB-SHEATHING, HORIZONTAL PURLINS
 NOR SIZE OF PURLINS OR SPACING. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7B) SHEET A-3 INDICATES THIS TO BE A PRE-ENGINEERED
 AWNING DOES THIS AWNING HAVE ENCLOSED ENDS AND IS THE
 BOTTOM ENCLOSED OR OPEN? THERE IS NO INFORMATION AS TO
 FRAMING SUPPORTS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 7C) SHEET A-3 THE PARAPET DETAIL NOTE # 5 INDICATES THE
 USE OF 6 INCH 16 GAUGE METAL STUDES FOR THE FRAMING OF
 THE PARAPET, ALSO SEE DETAIL # 3 INDICATES THE USE OF
 1/2 INCH CDX SHEATHING OR CMU (CONCRETE MASONRY UNITS).
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  