2015-07-31 09:29:59 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15070534 |
| ADD: 4117 BROADWAY |
| CONT: DREAMWORKS CONST. & REMOD. |
| TEL: (813)249-5541 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W |
| * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JULY 31/ 2015 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET INDICATES THE WIND DESIGN CRITERIA AS |
| 169 VULT, EXPOSURE C, THE POSITIVE AND NEGATIVE |
| PRESSURES ARE IN VULT WITH THE EXCEPTION OF ROOF ZONE # |
| 3, ZONE 3 PRESSURES ARE IN VASD. PLEASE SUBMIT ALL |
| PRESSURES IN VASD SINCE ALL PRODUCT APPROVALS ARE IN |
| VASD. |
| 2014 FBC-B 1609.3.1. |
| |
| 2) THE COVERSHEET LIST VARIOUS PRODUCT APPROVALS. |
| PLEASE SUBMIT THE ACTUAL PRODUCT APPROVALS FOR REVIEW |
| FOR CODE COMPLIANCE. |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. NOTE ALL GLAZING SIZES, TYPE OF |
| GLAZING, FASTENERS AND PRESSURES |
| (B) WINDOWS NOTE ALL GLAZING SIZES, TYPE OF GLAZING, |
| FASTENERS AND PRESSURES |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, NOTE ALL GLAZING SIZES, TYPE OF |
| GLAZING, FASTENERS AND PRESSURES |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, IDENTIFY WHICH |
| SUB-SYSTEM TO BE INSTALLED, IF LIMITATION # 7 ENHANCED |
| FASTENING, BY DESIGN PREFESSIONAL, |
| PROVIDE RAS 117 CALCULATIONS. |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 3) SHEET SP1-SP6: PROVIDE CURRENT PRODUCT APPROVALS |
| REVIEWED BY THE DESIGNER OF RECORD. |
| NOA 08-0715.03 09/11/2013 EXPIRED |
| NOA 09-0127.13 03/04/2014 EXPIRED |
| |
| 3A) SHEET A-2 INDICATES THE STOREFRONT GLAZYING SYSTEM |
| IS TO BE ALUMINUM FRAME, DOUBLE PIAN INSULATED CLEAR |
| TEMPERED IMPACT RESISTANT GLAZING. THE PRODUCT APPROVAL |
| TO BE SUBMITTED MUST MEET ALL OF THESE COMPONENTS, |
| |
| 4) 2014 FBC-ENERGY CODE PLEASE REVIEW C101.4.8 |
| EXCEPTIONS RENOVATED BUILDINGS MUST MEET THE 2014 |
| FBC-COMMERCIAL ENERGY. SEE DEFINITION OF RENOVATED |
| BUILDING. |
| |
| 2014 FBC-ENERGY DEFINITIONS: RENOVATED BUILDING. A |
| RESIDENTIAL OR NON-RESIDENTIAL BUILDING UNDERGOING |
| ALTERATIONS THAT VARIES OR CHANGES INSULATION, HVAC |
| SYSTEMS, WATER HEATER SYSTEMS OR, EXTERIOR ENVELOPE |
| CONDITIONS, PROVIDED THE ESTIMATED COST OF RENOVATION |
| EXCEEDS 30 % OF THE ASSESSED VALUE OF THE STRUCTURE. |
| THE P. B. C. PROPERTY APPRAISERS OFFICE HAS THE VALUE |
| OF THE STRUCTURE LISTED AT $64,656.00 AND THE VALUE OF |
| THE PERMIT APPLICATION IS LISTED AT $100,000.00. |
| |
| THE DESIGNER OF RECORD SHALL PROVIDE COMPLIANCE FOR THE |
| 2014 FBC-COMMERCIAL ENERGY C401.2 THROUGH EITHER THE |
| PRESCRIPTIVE REQUIREMENTS OR BY C407 PREFORMANCE BASED |
| TOTAL BUILDING PREFORMANCE BASED CALCULATIONS. |
| |
| 5) 2014 FBC-ACCESSIBILITY CODE SECTION 202.4.2 |
| DISPROPORTIONATE COST . ACCESSIBLE FEATURES IN THE |
| EVENT OF DISPROPORTIONATE COST. THE CONTRACT VALUE OF |
| THIS PROJECT IS $100,000.00 DOLLORS DISPROPORTION COST |
| ARE AT 20 % OF THE PROJECT OR $20,000.00 FOR ACCESIBLE |
| UPGRADES. THE FUNDS ARE TO BE SPENT ONACCESSIBLE |
| ELEMENTS FOR ACCESSIBLE ENTRANCES (NO STEPS, RAMPS |
| ENTRANCES), AN ACCESSIBLE ROUTE, ACCESSIBLE |
| RESTROOMSDRINKING FOUNTAINS. EITHER THE CONTRACTOR OR |
| DESIGN PROFESSIONAL IS TO SUBMIT A ITEMIZED REPORT |
| WHERE THESE MONIES WILL BE SPENT. |
| |
| 6) NOTE THE RESTROOMS DO NOT MEET THE 2010 |
| FBC-ACCESSIBLITY REQUIREMENTS, SEE 604.3.2 OVERLAP. |
| |
| 7A) SHEET A-2 INDICATES THIS TO BE A PRE-ENGINEERED |
| AWNING, BUT THERE IS NO WIND DESIGN CRITERIA, IS THIS |
| AWNING ONE THAT CAN BE REPOSITIONED IN THE EVENT OF A |
| HIGH WIND EVENT OR IS THIS A FIXED OPEN AWNING? SHEET |
| A-3 SHOWS A DETAIL OF THE SAME AWNING THE NOTES DO NOT |
| MENTION IF THERE IS A SUB-SHEATHING, HORIZONTAL PURLINS |
| NOR SIZE OF PURLINS OR SPACING. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 7B) SHEET A-3 INDICATES THIS TO BE A PRE-ENGINEERED |
| AWNING DOES THIS AWNING HAVE ENCLOSED ENDS AND IS THE |
| BOTTOM ENCLOSED OR OPEN? THERE IS NO INFORMATION AS TO |
| FRAMING SUPPORTS. 107.2.1.3 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 7C) SHEET A-3 THE PARAPET DETAIL NOTE # 5 INDICATES THE |
| USE OF 6 INCH 16 GAUGE METAL STUDES FOR THE FRAMING OF |
| THE PARAPET, ALSO SEE DETAIL # 3 INDICATES THE USE OF |
| 1/2 INCH CDX SHEATHING OR CMU (CONCRETE MASONRY UNITS). |
| 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |