Plan Review Notes
Plan Review Notes For Permit 15070508
Permit Number 15070508
Review Stop B
Sequence Number 2
Notes
Date Text
2015-10-06 15:32:13****CORRECTIONS****
 PLAN REVIEW IN PROGRESS
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROPERTY OWNER SENT PHOTOS WHICH I WAS TO REVIEW
 WHEN PLANS WERE RESUBMITTED. DUE TO THE LENGTH OF TIME
 SINCE THE PHOTOGRAPHS WERE SENT (TWO MONTHS), I NO
 LONGER HAVE THAT EMAIL.
  
 HOWEVER, BASED ON AERIALS, IT IS CLEAR THAT SOMETIME
 AFTER DECEMBER 2010, THE EAST AND SOUTH PARKING AREAS
 WERE SEALCOATED AND RESTRIPED, AND NO ACCESSIBLE
 PARKING WAS INSTALLED AS REQUIRED. INCORPORATE PARKING
 STRIPING INTO THE PLAN. ACCESSIBLE PARKING ON AN
 ACCESSIBLE ROUTE IS REQUIRED.
  
 2. PLAN SUBMITTED APPEARS REDUCED AND IS DIFFICULT TO
 READ. PROVIDE A FULL SIZE PLAN, FBC 107.FOR INSTANCE,
 LOOK AT THE TOP RIGHT; TITLE BLOCK, REVISION NUMBERS
 ARE NOT LEGIBLE. THE REMAINDER OF THE PAGE IS VERY
 SMALL AND DIFFICULT TO READ.
  
 3. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481. B2STUDIO APPEARS TO BE AN ARCHITECTURAL FIRM.
  
 4. RAMPS ARE TO HAVE LANDINGS AT THE TOP AND BOTTOM OF
 THE RAMP RUN, FBC 5TH EDITION ACCESSIBILITY 405.7.
 DETAIL 3 SHOWS A LANDING AT THE TOP, DETAIL 2 IS CALLED
 A RAMP DETAIL BUT DOES NOT SHOW LANDINGS AND SLOPE
 APPEARS MINIMAL. SPEC SLOPE ON PLAN.
  
 5. A 1/2" ELEVATION DIFFERENCE IS SHOWN AT WHAT APPEARS
 TO BE DOORWAYS (ACCESSIBLE ENTRANCES/EXITS). REVISE
 PLAN TO SHOW DOORS, DOOR SWING, MANEUVERING CLEARANCE
 FBC 5TH EDITION ACCESSIBILITY 305.7.
  
 6. "ADA ROUTE" IS SHOWN AS 4', NO WIDTH DIMENSION
 PROVIDED FOR WHAT APPEARS TO BE SIDEWALKS LEADING TO
 ACCESSIBLE ENTRANCES/EXITS.
  
 7. AS ADVISED, SEE COMMENT #1, REVISE PLAN TO
 INCORPORATE SEALCOATING AND STRIPING INTO THIS PLAN OR
 SUBMIT A SEPARATE APPLICATION. FAILURE TO DO SO MAY
 RESULT IN A VIOLATION ISSUED WITH 4X PERMIT FINE
 ASSESSED.
  
 SEALCOATING/RESTRIPE IS NOT WITHIN THE SCOPE OF A PAVER
 CONTRACTOR LICENSE. A SEPARATE PERMIT BY A CONTRACTOR
 LICENSED FOR THIS SCOPE IS REQUIRED.
  
 8. AS OWNER WAS UNABLE TO PROVIDE EVIDENCE OF A
 RESTRIPE PERMIT FOR THIS PROPERTY, REVISE PLANS TO
 INCLUDE THE FOLLOWING INFORMATION:
  
 REVISE PLAN TO PROVIDE THE FOLLOWING INFORMATION:
  
 TOTAL NUMBER OF PARKING SPACES
 NUMBER OF ACCESSIBLE SPACES
 LOCATION OF ACCESSIBLE ENTRANCES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 9. FBC 2010 ACCESSIBILITY 208.2.1, THE FOLLOWING USES
 HAVE ADDITIONAL PARKING REQUIREMENTS:
  
 HOSPITAL OUTPATIENT FACILITES
 REHABILITATION FACILITIES
 OUTPATIENT PHYSICAL THERAPY FACILITIES
  
 PLAN IS TO EITHER SHOW LOCATION OF TENANTS WITH ANY OF
 THE ABOVE USES OR PLAN IS TO INCLUDE A STATEMENT WHICH
 STATES THAT NONE OF THE ABOVE USES (HOSPITAL OUTPATIENT
 FACILITIES, REHABILITATION FACILITIES, OUTPATIENT
 PHYSICAL THERAPY FACILITIES) ARE AT THIS LOCATION.
  
  