Plan Review Notes For Permit 15070501 |
Permit Number |
15070501 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-23 11:25:23 | 1ST REVIEW: FBC 2014 MECHANICAL | | | | 1) PLEASE REMOVE THE AC CHANGE OUT FORM FROM THE PERMIT | | SUBMITTAL PACKAGE: THIS IS NOT A CHANGE OUT, IT IS A | | NEW INSTALLATION. | | 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN | | INDICATING THE MAKE AND MODEL NUMBERS OF THE CONDENSER | | AND THE AIR HANDLER, COOLING AND HEATING CAPACITIES, | | EFFICIENCY RATING, AND ELECTRICAL DATA. | | 3) CLARIFY THE SCOPE OF THE PROJECT WITH NOTES ON THE | | PLANS. INDICATE IF THE SYSTEM IS SUPPLEMENTAL TO A MAIN | | SYSTEM AND IDENTIFY THE ROOM IT IS CONDITIONING- | | BEDROOM, DEN, ENCLOSED PORCH? | | 4) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | CONDENSER PAD, AND WIND LOAD TIE DOWN ENGINNERING FOR | | THE CONDENSER PER MANUFACTURER'S SPECIFICATIONS- REFER | | TO SECTION M1401.4 FBC-10 RESIDENTIAL. | | 5) PROVIDE AN ELECTRICAL PLAN AND AN ELECTRICAL | | SUB-PERMIT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|