Plan Review Notes For Permit 15070489
Permit Number 15070489
Review Stop E
Sequence Number 2
Notes
Date Text
2015-09-10 21:07:31PREVIOUS NOTE 7 - THE ELECTRICAL DATUM PLANE AND
 DISCONNECTING REQUIREMNENTS ARE A FAIRLY NEW
 REQUIREMENT IN THE ELECTRICAL CODE AND NOT PREVIOUSLY
 ADDRESSED. PROVIDE AN ACTUAL ELEVATION FOR THE
 ELECTRICAL DATUM PLANE AND SHOW COMPLIANCE WITH THE NEC
 REQUIREMENTS.
 PREVIOUS NOTE 9 - IF THE ELECTRICAL DATUM PLANE IS NOT
 SHOWN AND ESTABLISHED, THE PLANS ARE NOT IN COMPLIANCE
 WITH THE GOVERNING ELECTRICAL REQUIREMENTS. COMPLETE
 REVIEW SHOULD REVEAL OTHER NON-COMPLIANT ITEMS.
 PREVIOUS NOTE 16 - PROVIDE INFORMATION TO THE FIELD
 INSPECTOR AT THE TIME OF THE INSPECTION SHOWING THE
 COMPATIBILITY AND LISTING INFORMATION OF THE COMPONENTS
 TO BE CONNECTED FOR SUITABILITY OF USE.