Date |
Text |
2015-07-31 08:27:04 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15070489 |
| ADD: 400 N. FLAGLER DR. DOCK E |
| CONT: CURRENT CONNECTIONS |
| TEL: (561)863-0010 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W |
| * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: |
| ACTION: DENIED |
| |
| 1) THE PLANS DO NOT PROVIDE THE MANUFACTURERS |
| SPECIFICATIONS FOR THE PEDESTALS NOR HAS THE ANCHORING |
| OF THE PEDESTALS TO THE DECK BEEN PROVIDED. PLEASE |
| PROVIDE ANCHORING OF PEDESTAL AND THE WIND DESIGN |
| CRITERIA PROVIDED FOR THE ANCHORING. |
| |
| |
| 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |