Date Text
2015-09-02 10:15:24PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SHALL SUBMIT A DATA SHEET FOR THE UNIMODE 600
 ANN. ( I TRIED TO GET THIS FOR YOU BUT WAS UNABLE TO)
 2. SMOKE DETECTOR IN MANAGER'S APARTMENT LIVING ROOM
 SHALL BE RELOCATED CLOSER TO THE BEDROOM, MAKE SURE TO
 STAY 3' FROM BATHROOM DOOR AND 10' FROM RANGE.
 3. LEVEL 2, UNIT 1 BEDROOM 2 MISSING S/D OUTSIDE OF
 DOOR. WHAT IS THAT WIC EXITING TO CORRIDOR? IF EXIT TO
 CORRIDOR WILL NEED A S/D AS WELL.
 4. LEVEL 2, UNIT 3 BEDROOM 2 MISSING S/D AS WELL.
 5. LEVELS 3 THROUGH LEVEL 7 ARE MISSING THE HEAT
 DETECTOR UNIT FROM THE LEGEND AS WELL AS THE TYPICAL
 MISSING S/D AS INDICATED ABOVE.
 6. LEVEL 8 UNITS 1 & UNIT 2 MISSING S/D FOR BEDROOM 2.
 7. MAY HAVE TO ADJUST LIVING ROOM S/D WITH RELATION TO
 THE BEDROOM DOOR.
 8. RISER AND CALCULATIONS MAY VARY DEPENDING ON HOW THE
 ABOVE CORRECTIONS ARE ADDRESSED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  