2015-09-02 10:15:24 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| |
| 1. YOU SHALL SUBMIT A DATA SHEET FOR THE UNIMODE 600 |
| ANN. ( I TRIED TO GET THIS FOR YOU BUT WAS UNABLE TO) |
| 2. SMOKE DETECTOR IN MANAGER'S APARTMENT LIVING ROOM |
| SHALL BE RELOCATED CLOSER TO THE BEDROOM, MAKE SURE TO |
| STAY 3' FROM BATHROOM DOOR AND 10' FROM RANGE. |
| 3. LEVEL 2, UNIT 1 BEDROOM 2 MISSING S/D OUTSIDE OF |
| DOOR. WHAT IS THAT WIC EXITING TO CORRIDOR? IF EXIT TO |
| CORRIDOR WILL NEED A S/D AS WELL. |
| 4. LEVEL 2, UNIT 3 BEDROOM 2 MISSING S/D AS WELL. |
| 5. LEVELS 3 THROUGH LEVEL 7 ARE MISSING THE HEAT |
| DETECTOR UNIT FROM THE LEGEND AS WELL AS THE TYPICAL |
| MISSING S/D AS INDICATED ABOVE. |
| 6. LEVEL 8 UNITS 1 & UNIT 2 MISSING S/D FOR BEDROOM 2. |
| 7. MAY HAVE TO ADJUST LIVING ROOM S/D WITH RELATION TO |
| THE BEDROOM DOOR. |
| 8. RISER AND CALCULATIONS MAY VARY DEPENDING ON HOW THE |
| ABOVE CORRECTIONS ARE ADDRESSED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |