Plan Review Notes
Plan Review Notes For Permit 15070442
Permit Number 15070442
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-15 17:49:50PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE FIRST FLOOR BEDROOM ON THE EAST END IS MISSING
 THE NOTIFICATION APPLIANCE.
 2. THAT SAME BEDROOM IS MISSING THE SMOKE DETECTOR
 REQUIRED ON THE OUTSIDE OF THE ROOM.
 3. ELEVATOR LOBBY MISSING RECALL DETECTOR.
 4. THE N.E. PARKING AREA MISSING NOTIFICATION
 APPLIANCE.
 5. TYPICAL TO FLRS. 2 ? 6 & 8:
 A) MISSING SMOKE DETECTOR IN ELEVATOR LOBBIES.
 B) SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN A
 RADIUS OF 10? FROM A COOKING APPLIANCE UNLESS
 SPECIFICALLY LISTED FOR THE PURPOSE.
 6. FLOOR PLAN FOR LEVEL 7 VARIES FROM THE REST; ROOMS
 SHALL BE LABELED FOR IDENTIFICATION.
 7. FLOOR 9 VARIES AS WELL, ALL ROOMS SHALL BE
 IDENTIFIED.
 8. BECAUSE THE DEVICE COUNT WILL VARY, THE RISER AND
 CALCS SHALL BE REVISED ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  