2015-07-15 17:49:50 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| 1. THE FIRST FLOOR BEDROOM ON THE EAST END IS MISSING |
| THE NOTIFICATION APPLIANCE. |
| 2. THAT SAME BEDROOM IS MISSING THE SMOKE DETECTOR |
| REQUIRED ON THE OUTSIDE OF THE ROOM. |
| 3. ELEVATOR LOBBY MISSING RECALL DETECTOR. |
| 4. THE N.E. PARKING AREA MISSING NOTIFICATION |
| APPLIANCE. |
| 5. TYPICAL TO FLRS. 2 ? 6 & 8: |
| A) MISSING SMOKE DETECTOR IN ELEVATOR LOBBIES. |
| B) SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN A |
| RADIUS OF 10? FROM A COOKING APPLIANCE UNLESS |
| SPECIFICALLY LISTED FOR THE PURPOSE. |
| 6. FLOOR PLAN FOR LEVEL 7 VARIES FROM THE REST; ROOMS |
| SHALL BE LABELED FOR IDENTIFICATION. |
| 7. FLOOR 9 VARIES AS WELL, ALL ROOMS SHALL BE |
| IDENTIFIED. |
| 8. BECAUSE THE DEVICE COUNT WILL VARY, THE RISER AND |
| CALCS SHALL BE REVISED ACCORDINGLY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |