Plan Review Notes
Plan Review Notes For Permit 15070400
Permit Number 15070400
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-09 09:12:129/9/15 MET WITH JIM PAINE TO GO OVER COMMENTS. TOLD HIM
 ALL THE COMMENTS BELOW NEED TO BE ADDRESSED. REVISED
 PLANS ARE REQUIRED. JG.
  
  
  
  
 **** BUILDING REVIEW COMMENTS FOR SUBMITTAL ADDRESSING
 PROVISO COMMENTS:
  
 1- REVISE BUILDING EXPOSURE AND ALL DESIGN PRESSURES.
 REVISE PLANS ACCORDINGLY. CLEARLY MARK THE DESIGN
 PRESSURES FOR ALL WINDOWS AND DOORS ON PLANS.
  
 2- PROVIDE COMPLETE DETAILS & SPECIFICATIONS FOR THE
 OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND
 OFFICE. SEC. R302.5. (ACCORDING TO ARCHITECT, IT WILL
 BE SUBMITTED LATER).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
  
 A) CUSTOM MADE MADE ENTRY DOOR ASSEMBLY AS SPECIFIED ON
 THE DOOR SCHEDULE (3-4" X 8'-0"). THERMA-TRU FLORIDA
 PRODUCT APPROVAL FL5891-R3 DOESN'T COVER THIS SIZE.
 ALSO, THE ENTRY DOOR ASSEMBLY SHOWS A SINGLE DOOR WITH
 TWO SIDELITES. PROVIDE PRODUCT APPROVAL FOR ENTIRE
 ASSEMBLY. IF THERE IS NOT PRODUCT APPROVAL, THEN
 PROVIDE COMPLETE ENGINEER PACKAGE FOR BUILDING OFFICIAL
 REVIEW/APPROVAL. CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) AT [email protected].
  
 B) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F" ON THE
 WINDOW SCHEDULE. NOA 11-1031.06 SUBMITTED DOESN'T COVER
 THAT SIZE. ( NOA 11-1031.06 DOESN'T COVER SIZE
 SPECIFIED ON THE WINDOW SCHEDULE (53" X 96").
  
 C) OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE
 PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4. (NOA
 13-0226.06 DOESN'T COVER SIZE SPECIFIED ON THE DOOR
 SCHEDULE (3'-4" X 8'-0").
  
 D) SLIDING GLASS DOORS WITH 3 PANELS SIZE AS SPECIFIED
 FOR DOOR #3. (REVISE PLANS AND DOOR SCHEDULE TO SHOW 4
 PANEL DOOR AS SPECIFIED ON THE LETTER SUBMITTED).
  
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA
 13-0321.07 SUBMITTED IS FOR 4", 6" & 12" LINTELS.
 (ACCORDING TO ARCHITECT IT WILL BE SUBMITTED LATER).
  
 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS.
  
 5- GEO-TECHNICAL ENGINEERING REPORT SUBMITTED NEED THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 F.S. (ACCORDING TO ARCHITECT, IT WILL BE
 SUBMITTED LATER).
  
 6- OWES $155.50 REVISION FEES FOR THIS SUBMITTAL.
  
 NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE
 REQUIRED DURING CONSTRUCTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]