2015-09-09 09:12:12 | 9/9/15 MET WITH JIM PAINE TO GO OVER COMMENTS. TOLD HIM |
| ALL THE COMMENTS BELOW NEED TO BE ADDRESSED. REVISED |
| PLANS ARE REQUIRED. JG. |
| |
| |
| |
| |
| **** BUILDING REVIEW COMMENTS FOR SUBMITTAL ADDRESSING |
| PROVISO COMMENTS: |
| |
| 1- REVISE BUILDING EXPOSURE AND ALL DESIGN PRESSURES. |
| REVISE PLANS ACCORDINGLY. CLEARLY MARK THE DESIGN |
| PRESSURES FOR ALL WINDOWS AND DOORS ON PLANS. |
| |
| 2- PROVIDE COMPLETE DETAILS & SPECIFICATIONS FOR THE |
| OPENING PROTECTION OF WINDOW LOCATED BETWEEN GARAGE AND |
| OFFICE. SEC. R302.5. (ACCORDING TO ARCHITECT, IT WILL |
| BE SUBMITTED LATER). |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| |
| A) CUSTOM MADE MADE ENTRY DOOR ASSEMBLY AS SPECIFIED ON |
| THE DOOR SCHEDULE (3-4" X 8'-0"). THERMA-TRU FLORIDA |
| PRODUCT APPROVAL FL5891-R3 DOESN'T COVER THIS SIZE. |
| ALSO, THE ENTRY DOOR ASSEMBLY SHOWS A SINGLE DOOR WITH |
| TWO SIDELITES. PROVIDE PRODUCT APPROVAL FOR ENTIRE |
| ASSEMBLY. IF THERE IS NOT PRODUCT APPROVAL, THEN |
| PROVIDE COMPLETE ENGINEER PACKAGE FOR BUILDING OFFICIAL |
| REVIEW/APPROVAL. CONTACT ROBERT BROWN (BUILDING |
| OFFICIAL) AT [email protected]. |
| |
| B) FIXED WINDOW SIZE SPECIFIED FOR WINDOW "F" ON THE |
| WINDOW SCHEDULE. NOA 11-1031.06 SUBMITTED DOESN'T COVER |
| THAT SIZE. ( NOA 11-1031.06 DOESN'T COVER SIZE |
| SPECIFIED ON THE WINDOW SCHEDULE (53" X 96"). |
| |
| C) OUTSWING GLAZED DOOR WITH SIDELITES: NEED TO PROVIDE |
| PRODUCT APPROVAL THAT COVERS SIZE FOR DOOR #4. (NOA |
| 13-0226.06 DOESN'T COVER SIZE SPECIFIED ON THE DOOR |
| SCHEDULE (3'-4" X 8'-0"). |
| |
| D) SLIDING GLASS DOORS WITH 3 PANELS SIZE AS SPECIFIED |
| FOR DOOR #3. (REVISE PLANS AND DOOR SCHEDULE TO SHOW 4 |
| PANEL DOOR AS SPECIFIED ON THE LETTER SUBMITTED). |
| |
| E) PRECAST LINTELS AS SPECIFIED ON PLANS. NOA |
| 13-0321.07 SUBMITTED IS FOR 4", 6" & 12" LINTELS. |
| (ACCORDING TO ARCHITECT IT WILL BE SUBMITTED LATER). |
| |
| 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS. |
| |
| 5- GEO-TECHNICAL ENGINEERING REPORT SUBMITTED NEED THE |
| ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY |
| CHAPTER 471 F.S. (ACCORDING TO ARCHITECT, IT WILL BE |
| SUBMITTED LATER). |
| |
| 6- OWES $155.50 REVISION FEES FOR THIS SUBMITTAL. |
| |
| NOTE: FLOOD ZONE A5. ELEVATION CERTIFICATES WILL BE |
| REQUIRED DURING CONSTRUCTION. |
| |