Plan Review Notes For Permit 15070311 |
Permit Number |
15070311 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-20 07:36:55 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS | | AND PANEL SCHEDULES TO SHOW THAT THE EXISTING SERVICE | | IS ADEQUATE FOR THE ADDITION OF THE POOL EQUIPMENT AND | | POOL HEATER. NEC 220.40 & FBC 107.3.5.3 |
|