2015-07-27 17:13:551ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070309
 7/27/15
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE AC
 SYSTEMS- REFER TO SECTION 13-407.1.ABC.1 FLORIDA
 BUILDING CODE 2004, OR THE CURRENT CODE IN EFFECT-
 SECTION C403.2.1 FLORIDA BUILDING CODE ENERGY
 CONSERVATION- 2014. PLEASE NOTE THAT 6-TONS OF COOLING
 FOR A 1026 SF. BUILDING SEEMS TO BE OVERSIZED- REFER TO
 SECTION C403.2.2. PLEASE ALSO NOTE THAT THE ELECTRICAL
 SCHEDULE ON SHEET A-1 DOES NOT SHOW CIRCUIT BREAKER
 SIZES FOR THE TWO 3 TON SYSTEMS WHICH SEEMS TO INDICATE
 THAT THESE SYSTEMS ARE BEING INSTALLED NEW: PLEASE
 CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER