2015-07-23 10:27:284920 LORING DRIVE - CONSTRUCTION TRAILERS
 PERMIT #15070309
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO - SUBMIT REVISION ADDRESSING PLAN REVIEW
 COMMENTS
  
 **A #131 FIRE FINAL INSPECTION IS NEEDED BEFORE
 OCCUPANCY OF THE STRUCTURE IS PERMITTED**
  
 DRAWING A1 INDICATES A "DOUBLE-WIDE" TRAILER STRUCTURE
 WITH DIMENSIONS OF 44' X 23' (1,012 SQ.FT.); HOWEVER,
 SITE PLAN DRAWING SP1 INDICATES A STRUCTURE AREA OF
 3,278 SQ.FT. PROVIDE AN ACCURATE PLAN SHOWING THE
 CONFIGURATIONS AND LOCATIONS OF THE TRAILERS.
  
 NO PLANS SUBMITTED FOR STAIRS, HANDRAILS OR GUARDRAILS.
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS,
 MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL
 BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS
 SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH
 OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 NOTE: CIVIL DRAWING 1 OF 2 INDICATES THE INSTALLATION
 OF A NEW FIRE HYDRANT AND NEW UNDERGROUND FIRE MAIN. A
 SEPARATE PLAN AND PERMIT (UG FIRELINE) IS REQUIRED FOR
 THIS WORK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  